Permit Number: T22CM00067
Parcel: 136238620

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00067
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. No note found regarding the use of the handwash sinks.[Second comment: Comment not addressed.] [Initial comment: Floor sinks and hand sinks in a kitchen are to discharge through a grease interceptor. Hand sinks (SK-1) in the kitchen are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, "HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED." Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson.]
2. No discernable changes made to the drawing of the drainage piping. [Second comment: Show the drainage fittings installed to guide sewage in the direction of flow. Reference: Section 706.3, IPC 2018. [Initial comment: Verify that the revised building drain from the kitchen area will drain through a grease interceptor and that the existing water closets are not draining through the grease interceptor. Reference: Sections 1003.2 and 1003.3.1, IPC 2018.]
3. The plumbing schematic and the plumbing floor plan are not coordinated. [Second comment: Comment not addressed. [Initial comment: Coordinate the plumbing schematic with the plumbing floor plan. Reference: Section 107.2.1, IBC 2018.]
4. No discernable changes made to the drawing of the drainage piping. [Second comment: Show the drainage fittings installed to guide sewage in the direction of flow. Reference: Section 706.3, IPC 2018. [Initial comment: Provide cleanouts for the new horizontal drain; the cleanouts shall be sized per Section 708.1.7, IPC 2018 and shall open to allow cleaning in the direction of flow. Reference: Sections 708.1.1 and 708.1.8, IPC 2018.]