Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T22CM00067
Parcel: 136238620

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00067
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/02/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Initial comment: Floor sinks and hand sinks in a kitchen are to discharge through a grease interceptor. Hand sinks (SK-1) in the kitchen are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, "HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED." Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson.]
2. Show the drainage fittings installed to guide sewage in the direction of flow. Reference: Section 706.3, IPC 2018. [Initial comment: Verify that the revised building drain from the kitchen area will drain through a grease interceptor and that the existing water closets are not draining through the grease interceptor. Reference: Sections 1003.2 and 1003.3.1, IPC 2018.]
3. Comment not addressed. [Initial comment: Coordinate the plumbing schematic with the plumbing floor plan. Reference: Section 107.2.1, IBC 2018.]
4. Show the drainage fittings installed to guide sewage in the direction of flow. Reference: Section 706.3, IPC 2018. [Initial comment: Provide cleanouts for the new horizontal drain; the cleanouts shall be sized per Section 708.1.7, IPC 2018 and shall open to allow cleaning in the direction of flow. Reference: Sections 708.1.1 and 708.1.8, IPC 2018.]