Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM00058
Parcel: 113103530

Address:
1402 E WATER ST

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM00058
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2022 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T22CM00058
Roof top Solar Panels (1st Review)
1402 E WATER ST

TRANSMITTAL DATE: January 19, 2022



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments

COMMENT: After comparing the aerials to the plot plan it has come to my attention that there is a possible non-permitted addition on the South portion of the house (Roof 3). After researching PRO there were no records for the addition that could be verified or found. If no permits are available relocate the solar panel away from the structure or a permit must be obtained for the addition.

COMMENT: Residential will review the application on the next submittal


If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans

Final Status

Task End Date Reviewer's Name Type of Review Description
01/20/2022 NGARCIA3 OUT TO CUSTOMER Completed