Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM00048
Parcel: 10819004A

Address:
4502 N 1ST AV

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T22CM00048
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2022 VFLORES1 COMMUNICATIONS REVIEW Approved
01/14/2022 JVINCEN1 FIRE REVIEW Approved
01/20/2022 SBLOOD1 ENGINEERING REVIEW Passed
01/20/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/28/2022 PETER MCLAUGHLIN ZONING REVIEW Completed
01/28/2022 PETER MCLAUGHLIN PLANNING-CITY HALL REVIEW Approved
02/02/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Ref; Plan Sheet E3.

1 . Provide a complete electrical line diagram and show all conductors, conduit sizes and types for the electrical service riser and if underground fed, the secondary conductor, conduit sizes and types.

2. What does "SBTC" mean for the grounding electrodes. Indicate this on the plan.

Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/02/2022 VVERA1 OUT TO CUSTOMER Completed