Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM00017
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/04/2022 | PCAMARE1 | OIP | REVIEW | Reqs Change | FROM: Paul Camarena PDSD Residential Review Section PROJECT: T22CM00017 TRANSMITTAL DATE: January 4, 2022 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed. COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments COMMENT: The pipe is undersized, based on a developed length of 75 ft a 3/4" pipe will provide 117,000. COMMENT: Residential will review the application on the next submittal If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans . |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/04/2022 | VVERA1 | OUT TO CUSTOMER | Completed |