Permit Review Detail
Review Status: Completed
Review Details: WALLS - SUBMITTAL
Permit Number - T22BU00331
Review Name: WALLS - SUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/23/2022 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Completed | |
| 09/07/2022 | IMONSHI1 | ZONING | REVIEW | Reqs Change | FROM: Iman Monshizadeh PDSD Zoning Review Section PROJECT: Retaining Wall Plot Plan Review (1st Review) LINDERBROOK DR / R-1 Zone TRANSMITTAL DATE: 09/07/2022 Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1.COMMENT: As per UDC section 6.6.2.I: Solid walls shall not be more that 6’ above grade, for walls higher than 6’ the additional length must be at least 75% permeable up to maximum of 10’. Additionally retaining walls may only extend 4’ below grade. Revise the details and sections provided to show that these standards are being met. If some details don’t apply to this project, remove them from the plans. UDC Section 6.6.2 : https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-5291 For questions regarding Zoning comments, please contact me at: Iman.Monshizadeh@tucsonaz.gov To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp |
| 09/07/2022 | IMONSHI1 | NPPO | REVIEW | Passed | |
| 09/20/2022 | SHASEMA1 | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/20/2022 | VVERA1 | OUT TO CUSTOMER | Completed |