Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22BU00318
Parcel: 117141580

Address:
136 W SIMPSON ST

Review Status: Completed

Review Details: POOL - SPA

Permit Number - T22BU00318
Review Name: POOL - SPA
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 International Swimming Pool and Spa Code and 2018 International Residential Code with amendments on 1/1/2019 along with requirements of the Arizona Revised Statute 36-1681. Show the current code reference on the plans.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration

SITE PLAN:

1. Show compliance with the pool enclosure barrier requirement by including a continuous 5 foot barrier around the pool, ARS 36-1681.
2. Show compliance with the pool barrier from a dwelling by including a UL 2017 listed pool alarm system for doors and windows open to the pool, or show a continuous barrier around the pool, 2018 ISPSC 305.4.1.
3. Show compliance with the overhead electrical line separation from the proposed pool location. A minimum of 10 foot horizonal and 22.5 foot diagonal separation is required, E4203.6.

STRUCTURAL PLANS:

1. Pool structures require a structural design by a registered engineer in the state of Arizona, R301.1.3.

MECHANICAL PLANS:

1. Provide an equipment specification list including the heater size or capacity, M1302.1.

ELECTRICAL PLANS:

1. Use Table E3705.5.3 for sizing 15, 20 & 30 AMP branch circuit conductors and protection ratings.
2. Use Table E3705.1, 60 degree C column, for sizing branch circuits and conductors rated at 100 AMP or less, E3705.4.1.
3. Bond the perimeter surface and reinforcing steel as required by ISPSC 302.1 and NEC680.26(B)(2).

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
09/08/2022 STEVE SHIELDS ZONING REVIEW Approved
09/08/2022 SBLOOD1 ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/08/2022 VVERA1 OUT TO CUSTOMER Completed