Permit Review Detail
Review Status: Completed
Review Details: POOL - COMM MODEL
Permit Number - T22BU00308
Review Name: POOL - COMM MODEL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/23/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
08/23/2022 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
08/30/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
08/30/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
09/01/2022 | WILDAN | BUILDING-COMMERCIAL | REVIEW | Completed | |
09/07/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1 Provide GFI protection for the Pool Pump. NEC 680.21(C). Pool Luminaires where applicable. 680.22. 2 Provide Outdoor Lighting Code compliance for the pool lighting. OLC section 104, 401.2.1(2), 402.1. Curfew requirements for unshielded lighting. 3 What type of underwater pool lighting is being utilized? Provide an electrical schematic of the pool lighting wiring. 4 Provide an electrical schematic for the Emergency Shut off Device. 5 Show the Equipotential Bonding in detail per NEC arts 680.26(A), (B). Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, City of Tucson Outdoor Lighting Code (OLC). |