Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22BU00308
Parcel: 132131110

Review Status: Completed

Review Details: POOL - COMM MODEL

Permit Number - T22BU00308
Review Name: POOL - COMM MODEL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2022 STEVE SHIELDS ZONING REVIEW Approved
08/23/2022 SSHIELD1 ENGINEERING REVIEW Passed
08/30/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/30/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/01/2022 WILDAN BUILDING-COMMERCIAL REVIEW Completed
09/07/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1 Provide GFI protection for the Pool Pump. NEC 680.21(C). Pool Luminaires where applicable. 680.22.

2 Provide Outdoor Lighting Code compliance for the pool lighting. OLC section 104, 401.2.1(2), 402.1. Curfew requirements for unshielded lighting.

3 What type of underwater pool lighting is being utilized? Provide an electrical schematic of the pool lighting wiring.

4 Provide an electrical schematic for the Emergency Shut off Device.

5 Show the Equipotential Bonding in detail per NEC arts 680.26(A), (B).

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, City of Tucson Outdoor Lighting Code (OLC).