Permit Number: T22BU00302
Parcel: 14011026A

Address:
2702 E BENSON HY

Review Status: Completed

Review Details: WALLS

Permit Number - T22BU00302
Review Name: WALLS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2022 AWARNER1 NPPO REVIEW Approved
08/16/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22BU00302
2702 E Benson Hwy. – C-2/R-1
Site Fence (1st Review)

TRANSMITTAL: August 16, 2022
This site is located in C-2 & R-1 Zone (UDC 4.7.21).

1. Based on the submitted plan it appears that this is an expansion of use area. Provide a copy of an approved commercial site plan that shows the site as depicted on the submitted plan. If you cannot provide an approved plan a new Development Package is required. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The DP is a separate submittal from the building plans and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using Submission Type “Site Review”.

2. As this site is made up of 3 parcels a lot combination is required. Provide a copy of the approved Pima Country Assessor’s Combo Request with the DP submittal.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/23/2022 SSHIELD1 ENGINEERING REVIEW Reqs Change Project: T22BU00302
Address: 2702 E Benson Hy – Site Fence
This project is within a mapped flood hazard area and requires a Floodplain Use Permit (FUP.)
Please start a new FUP at our permit application web page: https://docs.tucsonaz.gov/Forms/tucsonpermitapp.
Instructions:
1. Is this for a new or existing activity application? – Please select New Application.

2. Submission Type – Select Floodplain Use Permit.

3. Project Name – Enter a name for your project.

4. Type of Permit – Select Commercial or Residential (Residential is for work on single family residences and duplexes.)

5. Select Street Name from the list. You can type the first two letters or number to get closer to your choice in the list. Then select the rest of the address in the boxes provided.

6. Description of Work – Enter in Floodplain Use Permit for…and then put a description of the work being done or reference the building permit number associated with this floodplain use permit.

7. Complete the Applicant Info. (Note APA# is for applicants with an advance payment account. Leave blank is you do not have an APA account.

8. Complete the Contractor, Owner and Architect/Engineer sections as applicable.

9. Supporting Documentation Upload – Provide a complete cost estimate for the project unless it is for a new build/separate structure. You may also provide additional documents you think will be helpful.

10. Sign the application and submit.

Contact Loren Makus at Loren.Makus@tucsonaz.gov or Stephen Blood at Stephen.Blood@tucsonaz.gov if you have any questions about the FUP.
09/22/2022 WILDAN BUILDING-COMMERCIAL REVIEW Completed