Permit Number: T22BU00066
Parcel: 11518001A

Address:
1701 N ORACLE RD

Review Status: Active

Review Details: WALLS - ZONING/ENGINE

Permit Number - T22BU00066
Review Name: WALLS - ZONING/ENGINE
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2022 JGARCIA1 FIRE REVIEW Passed
09/07/2022 JGARCIA1 BUILDING-COMMERCIAL REVIEW Passed
10/20/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response
1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered Electrical design professional. Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements
10/20/2022 SHASEMA1 ENGINEERING REVIEW Reqs Change Project: T22BU00066

Address: 1701 N Oracle Rd

This project is within a regulated floodplain and requires a Floodplain Use Permit (FUP.)

Please start a new FUP at our permit application web page:

https://tdc-online.tucsonaz.gov/#/home

NOTE: A cost estimate from your contractor will be required if this project involves any reconstruction, repair, rehabilitation, structurally connected addition or other improvement of an existing structure (including TI’s). Construction of separate builds/new structures does not require a cost estimate to be provided.

Instructions:

1. Navigate into the current project in the “My Work” tab. Within the permit, navigate to the “Sub-Records” tab and click “Apply” on the Floodplain Use Permit Sub-Record

2. Locations -> Confirm the location is accurate to the project. Click “Next”

3. Type -> Fill in the “Square Feet” and “Valuation” boxes with the project area and a contractor-provided cost estimate (See note above: for new structures, input 0). Click “Next”

4. Contacts -> Confirm contacts and add any additional contacts if applicable. Click “Next”

5. More Info -> This will be filled in by the engineer assigned to your case, Click “Next”

6. Attachments -> Please attach the project plan, the source for the cost estimate (if applicable), and a drainage/hydrology report (if applicable). Click “Next”

7. Signature -> Read the statement and type your name. Sign your name below (You may Enable Type Signature to have the software sign for you.) Click “Next”

8. Review and Submit -> Review all information to ensure accuracy. Click “Submit”

Contact Scott Haseman at scott.haseman@tucsonaz.gov, Stephen Blood at Stephen.Blood@tucsonaz.gov, or Loren Makus at Loren.Makus@tucsonaz.gov if you have any questions about the FUP.
10/21/2022 STEVE SHIELDS ZONING REVIEW Reqs Change Unitl DP22-0213 by all review agenices Zoning cannot approve this plan.