Permit Number: T22BU00047
Parcel: 13101021A

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T22BU00047
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/09/2022 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Below are comments on the authorized repair submittal for COT ID# 315 at 1820 South Craycroft Road (T22BU00047)

Sheet 1 of 3

No comments.

Sheet 2 of 3

1, In 1st paragraph of Scope of Work, revise “temporarily remove” to “temporarily detach.

2. In 5th paragraph of Scope of Work, move the final parentheses from after “face” to after “pcs” to clarify that all of the numbers for all of forgoing parts are per face.

3. In 7th paragraph of Scope of Work, revise “Reinstall” to “Reattach”.

4. In Poster Panel Notes, insert the following standard language in place of the 4th paragraph: “In the course of top stringer removal, the 2-hole ¾” rigid conduit straps that secure the light fixture arm to the top stringers are removed, being held on by (4) 40d pole spikes. The existing top stringer on one face is then replaced with a new {like) stringer and the light fixture reattached with new {like) 3-hole ¾” conduit straps (2 pcs) and new (like) 4d pole spikes (4 pcs). The process is then repeated for the second face. No electrical components will be disconnected.”

5. In Poster Panel Side View, add depiction and designation for section rests (consistent with Detail A on Sheet 3).

6. In Poster Panel Top View, add ¾” straps to designations for bolts, indicate to be replaced with new (like), and extend to all four straps bolts, bolt.

7. In Poster Panel Top View, revise designation for lights from “temporarily removed and reinstalled” to “temporarily detached and reattached”.

8. In North Sign Face Elevation, revise designation for lights from “temporarily removed and reinstalled” to “temporarily detached and reattached”.

Sheet 3 of 3

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/09/2022 VVERA1 OUT TO CUSTOMER Completed