Permit Number: T22BU00029
Parcel: 116094210

Address:
3159 W SALVIA DR

Review Status: Completed

Review Details: POOL - SPA

Permit Number - T22BU00029
Review Name: POOL - SPA
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2022 SBLOOD1 ENGINEERING REVIEW Passed
02/16/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T22BU00029
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration

SITE PLAN:

1. Show compliance with the Pool Barrier requirement by including a continuous 5 foot barrier around the pool, ARS 36-1681.
2. Show compliance with the Pool Barrier requirement by including a UL 2017 listed pool alarm system for doors and windows open to the pool, or show a continuous barrier around the pool, 2018 ISPSC 305.4.1.

PLUMBING PLANS:

1. Notate and specify all piping materials, P2608.
2. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Provide a gas line isometric or table for showing the BTU demand and length of line to each gas appliance.

ELECTRICAL PLANS:

1. Use Table E3705.5.3 for sizing 15, 20 & 30 AMP branch circuit conductors and protection ratings.
2. Use Table E3705.1, 60 degree C column, for sizing branch circuits and conductors rated at 100 AMP or less, E3705.4.1.

If you have any questions, please contact:
Ken Van Karsen
(520) 791-5550
City of Tucson Residential Plan Review
02/17/2022 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22BU00029
Building Plan Review (1st Review)
3159 W SALVIA DR Zoning RX-2

TRANSMITTAL DATE: ?February ?17, ?2022


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1.COMMENT: Please address all residential comments.



If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
02/17/2022 NGARCIA3 OUT TO CUSTOMER Completed