Permit Number: T22BU00014
Parcel: 111084910

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22BU00014
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/08/2022 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC Transmittal

FROM: Loran Shamis
PDSD Zoning Review Section

PROJECT: T22BU00014
Cataline Towers - New Spa, and BBQ Area with shade stuctures
2475 N Haskell Dr

TRANSMITTAL DATE: August 08, 2022

DUE DATE: August 15, 2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

The proposed use is multifamily residential which is permitted in the O-3 zone (UDC, Table 4.8-3).

1. This comment was not addressed. COMMENT: As you are proposing improvements to a commercial site, an updated Development Package is required (UDC, 3.3.3). See Checklist for Minor Development Changes to Existing Commercial Sites - https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf

For questions regarding Zoning comments, please contact me at Loran.Shamis@tucsonaz.gov
To resubmit your plans for additional review, please visit: http://docs.tucsonaz.gov/Forms/tucsonpermitapp
08/10/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Comments from the previous electrical plan review were not addressed. There was no written response included with the re-submittal. Please address the previous comments, "Please provide complete electrical power and lighting plans. Include branch circuit and panel designations, grounding for the pool equipment, emergency shut off, panel schedules, indicate clearly all light fixture symbols and correlate with the luminaire schedule".

1 Provide a panel schedule verifying GFI protection for all pool Equipment, Receptacle(s), Lighting as required per NEC 680 Part 2.

2 Provide a grounding detail showing grounding and bonding of all Metallic Structural reinforcement, Ladders, Rails, Fencing, Equipotential Bonding, Motors, Metal Fittings (Components), etc. NEC Part 2.

3 Verify ‘Maintenace Disconnecting Means’ provided for the pool electrical equipment as required per NEC art 680.13.

4 Show wiring methods compliance per NEC art 680.14.

5 Verify receptacle locations comply with NEC art 680.22 were applicable.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code (OLC)
09/13/2022 JGARCIA1 BUILDING-COMMERCIAL REVIEW Completed