Permit Number: T22BU00014
Parcel: 111084910

Review Status: Completed

Review Details: POOL - COMM MODEL

Permit Number - T22BU00014
Review Name: POOL - COMM MODEL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet 2; New Spa: Please provide the spa gunite and reinforcing details as required, along with the spa standards and structural calculations.
2. Sheet 2; Renovated Pool and New Spa Plan: It appears there are two new shade structures at the new BBQ areas. Please provide structural calculations and details for these structures.
3. Sheet 2; Renovated Pool and New Spa Plan: Please provide structural calculations and details at the new deck as required.
4. Sheet 2; Revised Pool Section: Please provide details for the new pool floor connection to the existing pool floor.
5. General: Please provide written responses for all review comments.
01/26/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/26/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Specify the material to be used for the natural gas piping. Reference: Section 401.10, IFGC 2018.
02/09/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide complete electrical power and lighting plans, calculations, sealed by a Registrant registered in the State of Arizona. See City of Tucson Electrical Commercial Plan Submittal Requirements can be downloaded at www.tucsonaz.gov/pdsd.

Include branch circuit and panel designations, grounding for the pool equipment, emergency shut off, panel schedules, Indicate clearly all light fixture symbols and correlate with the luminaire schedule.

Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code for any altered or modified exterior lighting including pool underwater luminaires.

Ref; 2018 IBC sec. 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code
02/15/2022 SBLOOD1 ENGINEERING REVIEW Passed
02/16/2022 LSHAMIS1 ZONING REVIEW Reqs Change CDRC Transmittal

FROM: Loran Shamis
PDSD Zoning Review Section

PROJECT: T22BU00014
Cataline Towers - New Spa, and BBQ Area with shade stuctures
2475 N Haskell Dr

TRANSMITTAL DATE: February 16, 2022

DUE DATE: February 14, 2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

The proposed use is multifamily residential which is permitted in the O-3 zone (UDC, Table 4.8-3).

1. COMMENT: As you are proposing improvements to a commercial site, an updated Development Package is required (UDC, 3.3.3). See Checklist for Minor Development Changes to Existing Commercial Sites - https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf

For questions regarding Zoning comments, please contact me at Loran.Shamis@tucsonaz.gov
To resubmit your plans for additional review, please visit: http://docs.tucsonaz.gov/Forms/tucsonpermitapp
02/18/2022 JVINCEN1 FIRE REVIEW Approved