Permit Number: T21RW01337
Parcel: 999999999

Address:
1129 E PRINCE RD

Review Status: Completed

Review Details: ROW SWF - SUBMITTAL

Permit Number - T21RW01337
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2021 JSANDER1 START START Completed
03/29/2021 JSANDER1 IT_NETWK REVIEW Approved
03/30/2021 JSANDER1 HISTORIC Review Completed
04/01/2021 JSANDER1 DOT STREET MAINTENANCE REVIEW Approved
04/05/2021 RLEIGH1 DOT_WATER REVIEW Approved
04/05/2021 RICHARD LEIGH DOT ENGINEERING REVIEW Reqs Change Reviewer:
Richard Leigh
Richard.leigh@tucsonaz.gov

Engineering Drawings

Sheets SP1 & SP2: Photos are incorrect. Revise as necessary.

Temporary Traffic Control Plan

1. Revise TCP to address pedestrian considerations. ADA compliant pedestrian circulation shall be maintained through or around the worksite without directing pedestrians across the street.
04/07/2021 JSANDER1 DOT_ELEC REVIEW Reqs Change Sheets LS1 and C1 show 2 different mast arm lengths. Please correct to match existing.
04/07/2021 JSANDER1 REAL_ESTATE REVIEW Needs Review