Plan Number: T21PRE0276
Parcel: Unknown

Address:
3637 N 1ST AV

Review Status: Completed

Review Details: PREAPPLICATION LABELS

Plan Number - T21PRE0276
Review Name: PREAPPLICATION LABELS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2022 MROSS2 COT NON-DSD FIRE Completed D102.1 Access and loading.
Facilities, buildings or portions of buildings hereafter constructed shall be accessible to fire department apparatus by way of an approved fire apparatus access road with an asphalt, concrete or other approved driving surface capable of supporting the imposed load of fire apparatus weighting up to 75,000 pounds.

D103.4 Dead ends.
Dead-end fire apparatus access roads in excess of 150 feed shall be provided with width and turnaround provisions in accordance with Table D103.4.

FIRE HYDRANTS
507.5.1 Where required.
Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 400 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official.

Exceptions:

1. For Group R-3 and Group U occupancies, the distance requirement shall be 600 ft.

2. For buildings equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, the distance requirement shall be 600 feet.


Michael Ross
Tucson Fire Department
520-837-7082
Michael.Ross2@tucsonaz.gov
01/19/2022 LOREN MAKUS ENGINEERING REVIEW Completed 1. Drainage statement not required if 1 square foot of new water harvesting area, depressed 9 inches, is provided for each 12 square feet of new impervious area. Grades must direct discharge to the water harvesting areas.
Loren Makus
loren.makus@tucsonaz.gov
01/19/2022 AWARNER1 LANDSCAPE REVIEW Passed
01/20/2022 NMARTEL1 ZONING REVIEW Completed CDRC Thursday Pre-Submittal Transmittal
PDSD Zoning Review
FROM: Nicholas Martell, Planner
PROJECT: Thursday Pre-submittal meeting - T21PRE0276
Address: Parcel 10601229G
Zoning: C-2
Existing Use: Commercial Storage
Proposed Use: Commercial Storage
TRANSMITTAL DATE: January 20, 2022

COMMENTS:
1. Development must comply with the Administrative Manual Section 2-06 - Development Package.
2. Commercial Storage is permitted in the C-2 with 4.9.10.A as a use specific standard
3. Parking is calculated at 1 space per 5,000 square feet (Table 7.4.4-1 UDC).
4. Non-residential uses to non-residential zones have 0' setbacks adjacent to interior lots.
5. The proposed development is greater than a 25% expansion. Full code compliance is required.
6. Ensure access standards found in section 7.8 of the UDC and sections 7-01.0.0 and 10-01.0.0 of the Technical Standards Manual are met.
7. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards.
If you have any questions about this transmittal, contact me at Nicholas.Martell@tucsonaz.gov
01/20/2022 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Completed 300 - 330 pm - T21PRE0276 - 3637 N 1ST AV
Site More Than A Bed. Add 2500sf building

1. Tucson Water has no objections to the proposed development.

2. Any questions, comments or concerns about these comments may be directed to:

Tim Rowe, P.E., Civil Engineer
Tucson Water, New Development Section
310 W. Alameda St.
P.O. Box 27210
Tucson, AZ 85726-7210
(520) 837-2106
01/21/2022 JVWINKL1 COT NON-DSD TRAFFIC Completed T21PRE0276

1) Confirm that existing driveway apron meets PAG standard detail 206 for driveway aprons, including the use of detectable warnings. Update apron as needed

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov