Plan Number: T21PRE0197
Parcel: Unknown

Address:
9432 E 26TH ST

Review Status: Completed

Review Details: PREAPPLICATION LABELS

Plan Number - T21PRE0197
Review Name: PREAPPLICATION LABELS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2021 MROSS2 COT NON-DSD FIRE Completed None


Michael Ross
Tucson Fire Department
520-837-7082
Michael.Ross2@tucsonaz.gov
09/29/2021 IMONSHI1 ZONING REVIEW Completed FROM: Iman Monshizadeh

PDSD Zoning Review Section



PROJECT: T21PRE0197 – Well Upgrades – R-1 Zone – 9432 E 26th

TRANSMITTAL DATE: 09/29/2021



1.COMMENT:A Development Package will be required for this project. Information on the development package submittal requirements can be found at

https://www.tucsonaz.gov/files/pdsd/forms/Submittal_Requirements.pdf



Once the development package is approved then zoning can approved the commercial building plans.



2.COMMENT: Distribution systems are permitted in the Urban Residential Zones through a zoning examiner special exception procedure.



3.COMMENT: Show existing parking on the site plan as per utility use group parking requirements.



4.COMMENT: Use Specific Standards 4.9.11.A.1, .2, .5, .8, .9, .11 apply to this project:

https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-2930

Below are some that may be worth noting for this project.



1. The setback of the facility, including walls or equipment, shall be 20 feet from any adjacent residential zone.

2. The setback of the facility, including walls or equipment, shall be 200 feet from any existing adjacent residential zone. This setback may be varied in accordance with Sections 3.10.1 and 3.10.3, Board of Adjustment Variance Procedure.

8. Any building housing such facility shall be in keeping with the character of the zone in which it is located. The Design Review Board (DRB) shall review all applications and make recommendations to the Zoning Examiner. The DRB shall review architectural style, building elevations, materials on exterior facades, color schemes, new mechanical equipment locations, lighting of outdoor areas, window locations and types, screening, landscaping , vehicular use areas , and other contributing design features.

9. The use shall be located wholly within an enclosed building or within an area enclosed on all sides with a masonry wall or compact evergreen hedge, not less than six feet, nor more than ten feet, in height



For questions regarding Zoning comments, please contact me at: Iman.Monshizadeh@tucsonaz.gov

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp
09/30/2021 JVWINKL1 COT NON-DSD TRAFFIC Completed T21PRE0197

1) No adverse comments
09/30/2021 AWARNER1 LANDSCAPE REVIEW Passed
09/30/2021 SBLOOD1 ENGINEERING REVIEW Completed 1. This project is within a mapped flood hazard area and requires a Floodplain Use Permit.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
10/05/2021 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Passed