Plan Number: T21PRE0182
Parcel: Unknown

Review Status: Active

Review Details: PREAPPLICATION MEETING

Plan Number - T21PRE0182
Review Name: PREAPPLICATION MEETING
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2021 MROSS2 FIRE REVIEW Completed An automatic sprinkler system will be requried per IFC section 903.2.2.
A fire alarm system will be required per IFC section 907.2.2.1



Michael Ross
Tucson Fire Department
520-837-7082
Michael.Ross2@Tucsonaz.gov
09/14/2021 BILLIE LEE COMMENTS COMMENTS Active
09/14/2021 ANY URBAN PLANNING REVIEW Active
09/14/2021 ANY DOT ENGINEERING REVIEW Active
09/14/2021 LOREN MAKUS ENGINEERING REVIEW Completed 1. This site is not within a mapped flood hazard area.
2. Water harvesting must be maxmized.
3. Compliance with updated retention/detention manual is required. https://www.tucsonaz.gov/pdsd/codes-plans
09/15/2021 NICHOLAS ROSS ZONING REVIEW Completed Rezoning Pre-Submittal Transmittal

FROM: Nick Ross, Principal Planner
PDSD Zoning Review

PROJECT: Rezoning Pre-submittal meeting T21PRE0182
Address: 451 W. Auto Mall Dr.
Parcel(s): 104-08-052D
Existing Zoning: C-3
Proposed Zoning: C-3
Existing Use: Retail General Merchandise
Proposed Use: Medical Service Outpatient, Limited to blood donor centers

TRANSMITTAL DATE: September 14, 2021

COMMENTS:
1. Development must comply with the Administrative Manual Section 2-06 - Development Package.
2. Development standards: 87 units/acre, 75 ft height limit
3. Proposed use and use-specific standards: 4.9.4.O.3
4. Perimeter yard setbacks: 0 ft
5. Applicable overlays: n/a
6. Major Streets and Routes Plan: n/a
7. Applicable street setbacks: 20 ft or one and one-half the height of the building measured from the property line
8. Parking requirements: 1 space per 200sf of Medical Outpatient uses = 75 spaces
9. Bike parking requirements: Medical Outpatient uses = 1 space per 5,000sf short-term, 1 space per 12,000sf (min 2 spaces) long-term
10. Landscape requirements can be discussed further with Anne Warner at anne.warner@tucsonaz.gov.
11. Additional comments: Use Specific Standards that apply include - Blood donor centers shall comply with the following standards.
a. The site is not located in the same block as a residential zone or any elementary or secondary school or Day Care use.
b. The site is located at least 300 feet, measured in a straight line, from the property line to a residential zone boundary line or the property line of an elementary or secondary school.
c. A waiting area equal to 10% of the gross floor area is provided.
d. No other blood donor center is located within 1,200 feet.
12. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards.

If you have any questions please contact me at nicholas.ross@tucsonaz.gov.