Plan Number: T21PRE0170
Parcel: Unknown

Address:
2830 E MEDINA RD

Review Status: Completed

Review Details: PREAPPLICATION LABELS

Plan Number - T21PRE0170
Review Name: PREAPPLICATION LABELS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2021 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Completed 250 - 310 pm - T21PRE0170 - 2830 E MEDINA RD - SiteGradingSwppp: Tucson Airport Center, TAC2 B

1. Tucson Water's New Area Development Unit has no objections to the proposed development and offers the following comments for your convenience.

2. A Master Water Plan for TAC 2 A was prepared by VLMK and approved by Tucson Water in June 2021 which shows the closest water mains. This Master Water Plan will need to be revised to show the second building and how water will be supplied to it.

3. If new on-site fire hydrants are required by Tucson Fire., they will need to be public fire hydrants connected to public water mains.

4. The question regarding the need for an on-site fire loop of public water mains cannot be answered until Tucson Fire indicates if any on-site fire hydrants are necessary, where they need to be, and what the minimum fire flow is for the type of building construction. Hydraulic modeling may also be required to answer this question.

5. The question regarding the use of an electric fire pump will need to be answered by Tucson Fire.

6. There are no reclaimed water lines immediately adjacent to the site, and I am unaware of any requirement to utilize reclaimed water for irrigation purposes.

7. The above comments are based on the limited preliminary information provided by the applicant and should not be construed as a complete review of the proposal. Any questions, comments or concerns about these comments may be directed to:

Tim Rowe, P.E., Civil Engineer
Tucson Water, New Development Section
310 W. Alameda St.
P.O. Box 27210
Tucson, AZ 85726-7210
(520) 837-2106
08/18/2021 MROSS2 COT NON-DSD FIRE Completed 1. An automatic sprinkler system will be required.
2. A fire alarm system will be required

3. 507.1 Required water supply.
An approved water supply capable of supplying the required fire flow for the protection shall be provided to premises on which facilities, buildings or portions of buildings are hereafter constructed or moved into or within the jurisdiction.

507.3 Fire Flow.
Fire-flow requirements for buildings or portions of buildings and facilities shall be in accordance with Appendix B of the IFC.

4. FIRE HYDRANTS
507.5.1 Where required.
Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 400 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official.

Exceptions:
For buildings equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, the distance requirement shall be 600 feet.

507.5.1.1 Hydrant for standpipe systems.
Buildings equipped with a standpipe system installed in accordance with Section 905 shall have a fire hydrant within 100 feet of the fire department connections.
5. Aerial Fire Apparatus Access Roads
D105.1 Where required.
Where the vertical distance between the grade plane and the highest roof surface exceeds 30 feet, approved aerial fire apparatus access roads shall be provided.

D105.2 Width.
Aerial fire apparatus access roads shall have a minimum unobstructed width of 26 feet, exclusive of shoulders, in the immediate vicinity of the building or portion thereof.

D105.3 Proximity to building.
One or more of the required access routes meeting this condition shall be located not less than 15 feet and not greater than 30 feet from the building, and shall be positioned parallel to one entire side of the building. The side of the building on which the aerial fire apparatus access road is positioned shall be approved by the fire code official.



Michael Ross
Fire Code Inspector
Tucson Fire Department
520-837-7082
Michael.Ross2@tucsonaz.gov
08/18/2021 AWARNER1 LANDSCAPE REVIEW Completed CDRC TRANSMITTAL

TO: Planning and Development Services Department, Plans Coordination
FROM: Anne Warner, RLA
PDSD Landscape/NPPO Review
PROJECT: Industrial shell building
ACTIVITY NO. T21PRE0170
TRANSMITTAL DATE: August 18, 2021

7.6 Landscaping and Screening
The Unified Development Code (UDC) requires all new development or an expansion of greater than 25% of an existing development submit a landscape plan, UDC 7.6.2. Preparation of the landscape plan shall adhere to UDC 7.6.4. and Administrative Manual 2-10.

7.7. Native Plant Preservation
An approved Native Plant Preservation Plan Sections 7.7.4 is required or a request for an exception from the Native Plant Preservation requirements in accordance with Sections 7.7.3.D.3 & .4 of the Unified Development Code (UDC) and Admin. Manual Section 2-11.0.0 is required prior to Grading Plan approval.

UDC Technical Standards Manual – Section 4-01.0.0. Commercial Rainwater Harvesting and Section 5-01.0.0 Landscaping and Screening

If you have any questions about this transmittal, contact Anne Warner at email anne.warner@tucsonaz.gov
08/19/2021 JVWINKL1 COT NON-DSD TRAFFIC Completed T21PRE0170

1) A traffic impact analysis will be required for this development per Access Management Guidelines Section 6.3.2. Required improvements in the ROW will be determined as part of that process
2) Improvements along Country Club and Medina Rd will require a PIA.
3) Improvements along Country Club will need to account for the future ROW width of 120'

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
08/19/2021 NMARTEL1 ZONING REVIEW Completed CDRC Thursday Pre-Submittal Transmittal
PDSD Zoning Review
FROM: Nicholas Martell, Planner
PROJECT: Thursday Pre-submittal meeting - T21PRE0170
Address: Parcel 14042065B, 14042064B, 14042020A, 14042064A
Zoning: I-1
Existing Use: Vacant
Proposed Use: Shell-Warehouse/Manufacturing/Distribution/Office
TRANSMITTAL DATE: August 18, 2021

COMMENTS:
1. Development must comply with the Administrative Manual Section 2-06 - Development Package.
2. Refer to Table 4.8.7 of the Unified Development Code to determine permitted uses. Distribution, Commercial Storage, and Manufacturing are all permittable with some variables and use specific standards. Refer to article 4.9 for many of the applicable use-specific standards in the Industrial use group.
3. Parking is calculated as follows (Table 7.4.4-1 UDC); with variables:
a. Storage Use: 1 space per 5,000 square feet GFA
b. Industrial Use: 1 space per 1,000 square feet GFA
4. Non-residential uses to non-residential zones have 0' setbacks adjacent to interior lots.
5. Height maximums are 75' in the I-1 zone.
6. Ensure access standards found in section 7.8 of the UDC and sections 7-01.0.0 and 10-01.0.0 of the Technical Standards Manual are met.
7. Add ADA parking
8. A lot combination may be necessary before Development Package approval.
9. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards.
If you have any questions about this transmittal, contact me at Nicholas.Martell@tucsonaz.gov
08/24/2021 SBEASLE1 ENGINEERING REVIEW Needs Review