08/13/2021 AWARNER1 LANDSCAPE REVIEW Completed CDRC TRANSMITTAL

TO: Planning and Development Services Department, Plans Coordination
FROM: Anne Warner, RLA
PDSD Landscape/NPPO Review
PROJECT: Rook-Bellevue Homes
ACTIVITY NO. T21PRE0167
TRANSMITTAL DATE: August 19, 2021

7.6 Landscaping and Screening
The Unified Development Code (UDC) requires all new development or an expansion of greater than 25% of an existing development submit a landscape plan, UDC 7.6.2. Preparation of the landscape plan shall adhere to UDC 7.6.4. and Administrative Manual 2-10.

A 10’ street landscape border is required along streets. Interior 10' landscape borders are required adjacent to residential.

Water harvesting on site shall be maximized.

7.7. Native Plant Preservation
An approved Native Plant Preservation Plan Sections 7.7.4 required or a request for an exception from the Native Plant Preservation requirements in accordance with Sections 7.7.3.D.3 & .4 of the Unified Development Code (UDC) and Admin. Manual Section 2-11.0.0 is required prior to Grading Plan approval.

There are only a few trees on this site and plans may not be required, coordinate with the Landscape Section prior to Development Package submittal.


If you have any questions about this transmittal, contact Anne Warner at email anne.warner@tucsonaz.gov
08/17/2021 IMONSHI1 ZONING REVIEW Completed FROM: Iman Monshizadeh

PDSD Zoning Review Section

PROJECT: T21PRE0167 – Rook-Bellevue Homes- R-3 Zone

TRANSMITTAL DATE: 08/17/2021


1.COMMENT: A Development Package will be required for this project. Information on the development package submittal requirements can be found at

https://www.tucsonaz.gov/files/pdsd/forms/Submittal_Requirements.pdf



Once the development package is issued then the commercial building plans that are consistent with the development package can be issued.



2.COMMENT: Parcel 12108048A and 12108047A will need to be combined prior to the approval of this project.



3.COMMENT: Front perimeter yard setbacks for established areas will be 20’ or 1½ * Height (whichever is greater) from the structure to the property line. Rear and side perimeter yard setbacks will be 10’ or ¾ * Height (whichever is greater) from the structure to the property line. Building height may affect current proposed setbacks.



4. COMMENT: Parking calculations for multifamily developments are based on bedroom count per unit.



For questions regarding Zoning comments, please contact me at: Iman.Monshizadeh@tucsonaz.gov

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp
08/17/2021 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Completed 150 - 210 pm - T21PRE0167 - 6207 E BELLEVUE ST - Final Plat: Rook-Bellevue Homes

1. Tucson Water's New Area Development Unit has no objections to the proposed development and offers the following comments for your convenience.

2. The proposed water mains will need to be located in public streets, or in private streets (common areas) dedicated as public utility easements.

3. If the proposed water mains cannot be constructed for less than $50,000, the design of the proposed water mains must be reviewed and approved in Tucson Water's Master Water Plan and Design Plan review processes.

4. The above comments are based on the limited preliminary information provided by the applicant and should not be construed as a complete review of the proposal. Any questions, comments or concerns about these comments may be directed to:

Tim Rowe, P.E., Civil Engineer
Tucson Water, New Development Section
310 W. Alameda St.
P.O. Box 27210
Tucson, AZ 85726-7210
(520) 837-2106
08/18/2021 MROSS2 COT NON-DSD FIRE Completed FIRE HYDRANTS

507.5.1 Where required.
Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 400 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official.

D102.1 Access and loading.
Facilities, buildings or portions of buildings hereafter constructed shall be accessible to fire department apparatus by way of an approved fire apparatus access road with an asphalt, concrete or other approved driving surface capable of supporting the imposed load of fire apparatus weighting up to 75,000 pounds.


Michael Ross
Fire Code Inspector
Tucson Fire Department
520-837-7082
Michael.Ross2@tucsonaz.gov
08/18/2021 SBLOOD1 ENGINEERING REVIEW Completed 1. Maximize water harvesting.
2. Show the solid waste collection maneuverability with dimensions to ensure adequate space to pull in and back out.
3. The sidewalk on both sides of the access loop needs to be 4' per COT standards.
4. Site must be provided with balanced basin detention and first flush retention as per new detention/retention manual https://www.tucsonaz.gov/pdsd/codes-plans

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
08/19/2021 JVWINKL1 COT NON-DSD TRAFFIC Completed T21PRE0167

1) No adverse comments, standard details apply