08/11/2021 LSHAMIS1 ZONING REVIEW Completed CDRC Thursday Pre-Submittal Transmittal
PDSD Zoning Review

FROM: Loran Shamis; Planner, MBA

PROJECT: Thursday Pre-submittal meeting - T21PRE0163
Address: 820 E Tucson Marketplace Bl
Parcel(s): 13213113A
Zoning: PAD-15, Subarea B-IV
Existing Use: Vacant
Proposed Use: Personal Storage

TRANSMITTAL DATE: August 12, 2021

COMMENTS:
1. Development must comply with the Administrative Manual Section 2-06 - Development Package.
2. The proposed use is personal storage, which is permitted in the PAD-15 Subarea IV, with use specific standards 4.9.10.C.3 and .6 are applicable (UDC, Table 4.8-4).
3. The maximum permitted height is 99' (PAD-15, Section C.2.3, Table E).
4. The minimum building setback is 50' measured from the property line (PAD-15, Section C.2.3, Table E).
5. The required parking calculation for Personal Storage is 1 space per 4,000 sq ft gross floor area if storage units do not have direct vehicular access and a minimum of 2 spaces for any associated office (UDC, Table 7.4.4-1).
6. The required bicycle parking calculation for Personal Storage is 2 short term bicycle parking spaces are required (UDC, 7.4.8-1)
7. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards.

If you have any questions, please contact me at Loran.Shamis@tucsonaz.gov.
To submit your plans for review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp
08/11/2021 MROSS2 COT NON-DSD FIRE Completed - An automatic fire sprinkler system will be required.
- A fire alarm system will be required.
-D104.1 Building exceeding three stories or 30 feet in height.
Buildings or facilities exceeding 30 feet or three stories in height shall have not fewer than two means of fire apparatus access for each structure.

D104.3 Remoteness.
Where two fire apparatus access roads are required, they shall be placed a distance apart equal to not less than one half of the length of the maximum overall diagonal dimension of the lot or area to be served, measured in a straight line between accesses.

Aerial Fire Apparatus Access Roads
D105.1 Where required.
Where the vertical distance between the grade plane and the highest roof surface exceeds 30 feet, approved aerial fire apparatus access roads shall be provided.

D105.2 Width.
Aerial fire apparatus access roads shall have a minimum unobstructed width of 26 feet, exclusive of shoulders, in the immediate vicinity of the building or portion thereof.

D105.3 Proximity to building.
One or more of the required access routes meeting this condition shall be located not less than 15 feet and not greater than 30 feet from the building, and shall be positioned parallel to one entire side of the building. The side of the building on which the aerial fire apparatus access road is positioned shall be approved by the fire code official.

507.3 Fire Flow.
Fire-flow requirements for buildings or portions of buildings and facilities shall be in accordance with Appendix B of the IFC.

-A fire hydrant is required to be within 600' of all portions of the building. Any standpipe system connection is required to be withing 100' of a hydrant.

-Buildings over 35' tall are required to be tested for ERRC (Emergency Responder Radio Coverage).




Michael Ross
Fire Inspector
Tucson Fire Department
520-837-7082
Michael.Ross2@tucsonaz.gov
08/11/2021 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Completed 150 - 210 pm - T21PRE0163 - 820 E TUCSON MARKETPLACE BL - SiteGrading The Bridges Lot 10-B

1. Tucson Water's New Area Development Unit has no objections to the proposed development, and offers the following comments for your convenience.

2. A water main in a 15' wide water-line easement is be installed along the north side of the proposed development under Plan No. 098-2019, and no permanent structures may be constructed within this easement.

3. The above comments are based on the limited preliminary information provided by the applicant and should not be construed as a complete review of the proposal. Any questions, comments or concerns about these comments may be directed to:

Tim Rowe, P.E., Civil Engineer
Tucson Water, New Development Section
310 W. Alameda St.
P.O. Box 27210
Tucson, AZ 85726-7210
(520) 837-2106
08/12/2021 JVWINKL1 COT NON-DSD TRAFFIC Completed no adverse comments
08/12/2021 SBLOOD1 ENGINEERING REVIEW Completed Maximize water harvesting.
08/12/2021 AWARNER1 LANDSCAPE REVIEW Completed CDRC TRANSMITTAL

TO: Planning and Development Services Department, Plans Coordination
FROM: Anne Warner, RLA
PDSD Landscape/NPPO Review
PROJECT: CAP Self Storage
ACTIVITY NO.: T21PRE0163
TRANSMITTAL DATE: August 12, 2021

7.6 Landscaping and Screening
The Unified Development Code (UDC) and PAD-15 documents requires all new development submit a landscape plan, UDC 7.6.2. Preparation of the landscape plan shall adhere to UDC 7.6.4. and Administrative Manual 2-10.

If you have any questions about this transmittal, contact Anne Warner at email anne.warner@tucsonaz.gov