Plan Number: T21PRE0147
Parcel: Unknown

Review Status: Completed

Review Details: PREAPPLICATION LABELS

Plan Number - T21PRE0147
Review Name: PREAPPLICATION LABELS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2021 AWARNER1 LANDSCAPE REVIEW Passed
07/12/2021 MROSS2 COT NON-DSD FIRE Completed 1. Fire apparatus access roads shall have an unobstructed width of not less than 20 feet and an unobstructed vertical clearance of not less than 15'.


Michael Ross
520-837-7082
Michael.Ross2@tucsonaz.gov
07/13/2021 LOREN MAKUS ENGINEERING REVIEW Completed T21PRE0147
1. Site is not within any mapped flood hazard area.
2. The lot dimensions in the plans and exhibits sheet 3 are not consistent with the dimensions of the existing conditions on sheet 4.
3. Water and sewer are in Fremont Avenue. Sewer easements will be required for the rear lots. See water comments for water requirements.
4. A 5-foot sidewalk is required along the Fremont Avenue frontage.
07/13/2021 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Completed 250 - 310 pm - T21PRE0147 - 1016 S FREMONT AV - Minor Subdivision Fremont Properties

1. Each of the five proposed lots MUST have a separate water meter, as they will eventually be under different ownership.

2. To comply with Tucson Water's Remote Meter Policy, that prohibits water service lines from being run across property that will under different ownership in private easements:
a. Each of the five proposed lots must have a minimum of 15' of actual real property frontage on the existing 6" cement asbestos water main in Fremont Ave (PN 024-1964). i.e. Lots B &E would need to be reconfigured as "flag pole" lots that front the existing water main in Fremont Ave, OR
b. The developer will need to construct a new public water main in the alley to serve Lots B & E.

3. The design of the new public water main would need to be reviewed and approved within Tucson Water's Water Master Plan and Design Plan Review Processes.

4. The above comments are based on the limited preliminary information provided by the applicant and should not be construed as a complete review of the proposal. Any questions, comments or concerns about these comments may be directed to:

Tim Rowe, P.E., Civil Engineer
Tucson Water, New Development Section
310 W. Alameda St.
P.O. Box 27210
Tucson, AZ 85726-7210
(520) 837-2106
07/15/2021 JVWINKL1 COT NON-DSD TRAFFIC Completed T21PRE0147

1) Upon construction new 5' wide sidewalk will need to be provided along S Fremont Av
2) Upon construction any un-used curb cuts along S Fremont Av will need to be closed off. Driveways will need to be constructed according to PAG standard detail 206
3) Any work or improvements in the alley would require a public improvement agreement

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
07/15/2021 IMONSHI1 ZONING REVIEW Completed FROM: Iman Monshizadeh

PDSD Zoning Review Section



PROJECT: T21PRE0147 – Minor Subdivision

1016 South Freemont – R-2 Zone



TRANSMITTAL DATE: 7/15/21





1.COMMENT: Street frontage for all lots may be required by Tucson Water. The proposed lot do meet the zoning requirements for an R-2 Zone.



2.COMMENT: Per UDC Article 7.4.6.K an alley can be used for access as long as it meets the requirements of UDC Article 7.4.6.K.2. PDSD would also allow the use of an easement for access to the proposed properties on the west if required.



3.COMMENT: Perimeter yard setbacks are dependent on the ADT of the street. ADT can be calculated using the table in section 10-01.2.2 in the Technical Standards Manual. Below is a link to the table.

https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-12249





If you have any questions about this transmittal, Contact Iman Monshizadeh by email Iman.Monshizadeh@tucsonaz.gov or contact Elisa Hamblin, at Elisa.Hamblin@tucsonaz.gov