Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Plan Number: T21PRE0135
Parcel: Unknown

Review Status: Completed

Review Details: PREAPPLICATION LABELS

Plan Number - T21PRE0135
Review Name: PREAPPLICATION LABELS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2021 AWARNER1 LANDSCAPE REVIEW Completed FROM: Anne Warner, RLA
PDSD Landscape/NPPO Review
PROJECT: QuikTrip, 920 E Tucson Mktpl
T21PRE0135

TRANSMITTAL DATE: July 1, 2021

This project is subject to The Bridges PAD-15 landscape requirements.

UDC Article 7.6 Landscaping and Screening
The Unified Development Code (UDC) requires all new development or an expansion of greater than 25% of an existing development submit a landscape plan, UDC 7.6.2. Preparation of the landscape plan shall adhere to UDC 7.6.4. and Administrative Manual 2-10.

UDC Technical Standards Manual – Section 4-01.0.0. Commercial Rainwater Harvesting and Section 5-01.0.0 Landscaping and Screening. The Bridges doesn't require a formal Water Harvesting plan submittal, but does require that the water harvesting is maximized through site design.


If you have any questions about this transmittal, Contact Anne Warner at my email, anne.warner@tucsonaz.gov
06/28/2021 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Completed 150-210 pm - T21PRE0135 - 920 E Tucson Mktpl - SiteGrading QuikTrip Store

1. Tucson Water's New Area Development Unit has no objections to the proposed development

2. The above comments are based on the limited preliminary information provided by the applicant and should not be construed as a complete review of the proposal. Any questions, comments or concerns about these comments may be directed to:

Tim Rowe, P.E., Civil Engineer
Tucson Water, New Development Section
310 W. Alameda St.
P.O. Box 27210
Tucson, AZ 85726-7210
(520) 837-2106
06/30/2021 MROSS2 COT NON-DSD FIRE Completed None


Michael Ross
520-837-7082
Michael.Ross2@tucsonaz.gov
06/30/2021 NMARTEL1 ZONING REVIEW Completed CDRC Thursday Pre-Submittal Transmittal
PDSD Zoning Review
FROM: Nicholas Martell, Planner
PROJECT: Thursday Pre-submittal meeting - T21PRE0135
Address: 920 E Tucson Marketplace Bl, Parcel: 132131090
Zoning: PAD-15
Existing Use: Vacant
Proposed Use: Retail-General Merchandise Sales
TRANSMITTAL DATE: June 30, 2021

COMMENTS:
1. Development must comply with the Administrative Manual Section 2-06 - Development Package.
2. The land uses in the B-IV area of PAD-15 are subject to the uses permitted by the OCR-1 zone in the Unified Development Code. General Merchandise Sales is a permitted use in the OCR-1 zone with the use specific standard 4.4.4.B.1
3. The property is in Zone 3 of Sub Area B-IV in PAD-15. The maximum building height is 99'; the minimum building setback from any public street and/or MS&R is 20'; and the minimum building setback from I-10 is 50', measured from the property line.
3. Parking calculations are according to section 7.4 of the UDC. However, Motor Vehicle Spaces for a retail use require a minimum of 4 spaces for each 1,000 square feet of Gross Floor Area (GFA). Parking stall counts may be done across each Sub-Area, subject to a recorded cross-parking agreement for the overall Sub-Area.
4. Bike parking is required at 1 space per 5,000 sq. ft. GFA (short term) and 1 space per 12,000 sq. ft. GFA. Each carries a mandatory minimum of 2 spaces.
5. Ensure access standards found in section 7.8 of the UDC and sections 7-01.0.0 and 10-01.0.0 of the Technical Standards Manual are met.
6. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards.
If you have any questions about this transmittal, contact me at Nicholas.Martell@tucsonaz.gov
07/01/2021 JVWINKL1 COT NON-DSD TRAFFIC Completed T21PRE0135

1) Confirm that this gas station was accounted for in the Bridges Traffic Impact Analysis. If not an update to the TIA or a new TIA will be required
2) The driveway entrance/exit on to E Tucson Marketplace Bl, does not meet City of Tucson Access Management guidelines Figure 5-4. It is understood that this is a Private Drive. The driveway needs to be shifted about 40 feet to the west to provide proper clear space at the Park Av intersection.

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
07/01/2021 LOREN MAKUS ENGINEERING REVIEW Completed 1. Site is in estimated floodplain. If this has not been mitigated by drainage improvements a floodplain use permit is required.
2. Address critical basin detention and first flush retention. If this is managed by the regional basin, show conformance with the master drainage plan.
3. Maximize water harvesting.
Loren Makus, EIT
Loren.makus@tucsonaz.gov