Plan Review Detail
Review Status: Completed
Review Details: PREAPPLICATION LABELS
Plan Number - T21PRE0126
Review Name: PREAPPLICATION LABELS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/02/2021 | AWARNER1 | LANDSCAPE | REVIEW | Completed | FROM: Anne Warner, RLA PDSD Landscape/NPPO Review PROJECT: 6251 S Kolb Rd, Valencia Distribution, PAD-26 T21PRE0126 TRANSMITTAL DATE: June 10, 2021 The Landscape and Native Plant Preservation requirements are subject to the requirements of PAD-26, which includes the original South Kolb Specific Plan as well as the South Kolb Specific Plan Amendment. Specific 15’ wide bufferyard (landscape border) requirements are described in these documents for the DMAFB boundary and Valencia Road (Scenic Corridor). Demonstrate compliance with these requirements. If you have any questions about this transmittal, Contact Anne Warner by email anne.warner@tucsonaz.gov |
| 06/08/2021 | MROSS2 | COT NON-DSD | FIRE | Completed | 1. FIRE HYDRANTS 507.5.1 Where required. Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 400 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official. Exceptions: -For Group R-3 and Group U occupancies, the distance requirement shall be 600 ft. -For buildings equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, the distance requirement shall be 600 feet. 2.Automatic fire sprinkler system will be required. 3. Fire alarm system will be required. 4. EMERGENCY RESPONDER RADIO COVERAGE 510.1 Emergency responder radio coverage in new buildings. New buildings shall have approved radio coverage for emergency responders within the building based on the existing coverage levels of the public safety communication systems utilized by the jurisdiction, measured at the exterior of the building. This section shall not require improvement of the existing public safety communication systems. 5. Aerial Fire Apparatus Access Roads D105.1 Where required. Where the vertical distance between the grade plane and the highest roof surface exceeds 30 feet, approved aerial fire apparatus access roads shall be provided. D105.2 Width. Aerial fire apparatus access roads shall have a minimum unobstructed width of 26 feet, exclusive of shoulders, in the immediate vicinity of the building or portion thereof. D105.3 Proximity to building. One or more of the required access routes meeting this condition shall be located not less than 15 feet and not greater than 30 feet from the building, and shall be positioned parallel to one entire side of the building. The side of the building on which the aerial fire apparatus access road is positioned shall be approved by the fire code official. Michael Ross 520-837-7082 Michael.Ross2@tucsonaz.gov |
| 06/09/2021 | LOREN MAKUS | ENGINEERING | REVIEW | Completed | 1. Show ADC-2 area on Development Package. Clearly delineate all airport/DM related overlays as well. 2. Site is in balanced basin, contributing to two separate watersheds. Balanced basin detention is required. 3. Provide first-flush retention per the newly effective detention/retention manual with City of Tucson amendments. 4. Water harvesting must be maximized. 5. Provide waste stream calculations and demonstrate adequate capacity and access. |
| 06/10/2021 | JVWINKL1 | COT NON-DSD | TRAFFIC | Completed | T21PRE0126 1) Just east on Valencia, there is a driveway entrance which was constructed as an approved access point to the development. Clarify if it is being used 2) The proposed entrance off S Kold Rd will likely need to be to be signalized. 3) The southern most entrance along E Valencia Rd will need to provide proper site visibility distances and likely needs signalization in order to accommodate the left out 4) The Unnamed Rd will not accommodate cross traffic due to existing large traffic volumes. The Proposed eastern most entrance, directly north of the existing access to the property to the south will need to be removed 5) Additional meetings with Traffic Engineering are recommended 6) An updated traffic impact analysis will be required per city of Tucson Access Management Guidelines section 6 7) Show on plans new 6' wide sidewalk along project frontage on S Kolb Rd per City of Tucson Technical Standards Manual Section 10 8) The final plat indicates that Riparian Mitigation In-Lieu fees are part of this development. Please contact Eric Shepp and Pima County Regional Flood Control District, Eric Shepp <Eric.Shepp@pima.gov> John Van Winkle, P.E. John.VanWinkle@tucsonaz.gov |
| 06/10/2021 | SAMUEL ROGERS | ZONING | REVIEW | Completed | CDRC Thursday Pre-Submittal Transmittal PDSD Zoning Review FROM: Samuel Rogers, Planner PROJECT: Thursday Pre-submittal meeting - T21PRE0126 Address: 6251 S KOLB RD Parcel(s): 141-06-009H Zoning: PAD-26 Existing Use: Vacant Proposed Use: Commercial Storage TRANSMITTAL DATE: COMMENTS: 1. Development must comply with the Administrative Manual Section 2-06 - Development Package. 2. The use appears to be either Transportation Service - Land Carrier or Commercial Storage. If items are shipped directly to customers it will be consider Transportation Service. If items are shipped to other businesses, it will be considered Commercial Storage. 3. Parking for Transportation Service is required at 1 space per 300 sq ft of GFA of administrative or professional office only. 4. Parking for Commercial Storage is required at 1 space per 5,000 Sq ft of G.F.A. 5. The minimum building setback for Kolb Road is 30 feet and Valencia Road is 60 feet 6. The sides, front, and roof lines of buildings visible from Valencia and Kolb Roads shall be designed such that they jog, have slight projections or material changes or are interrupted by landscaping in order to avoid a monotonous appearance, in accordance with the Scenic Routes Ordinance. 7. Provide documentation that all PAD requirements have been met. 8. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards. If you have any questions please contact me at Samuel.Rogers@tucsonaz.gov or (520) 837-6932. |
| 06/15/2021 | SBEASLE1 | TUCSON WATER NEW AREA DEVELOPMENT | REVIEW | Needs Review |