Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Plan Number: T21PRE0118
Parcel: Unknown

Review Status: Completed

Review Details: PREAPPLICATION LABELS

Plan Number - T21PRE0118
Review Name: PREAPPLICATION LABELS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2021 AWARNER1 LANDSCAPE REVIEW Passed
05/25/2021 JVWINKL1 COT NON-DSD TRAFFIC Completed T21PRE0118

No adverse comments
05/25/2021 MROSS2 COT NON-DSD FIRE Completed None
05/26/2021 LSHAMIS1 ZONING REVIEW Completed CDRC Thursday Pre-Submittal Transmittal
PDSD Zoning Review

FROM: Loran Shamis; Planner, MBA

PROJECT: Thursday Pre-submittal meeting – T21PRE0118
Address: 2801 E Waverly St
Parcel(s): 123041210
Zoning: R-1
Existing Use: Distribution System – Well Site
Proposed Use: Distribution System – Well Site Upgrades

TRANSMITTAL DATE: May 27, 2021

COMMENTS:
1. Development must comply with the Administrative Manual Section 2-06 - Development Package.
2. The proposed use is Distribution System, which is permitted through a Zoning Examiner Special Exception Procedure. Use specific standards are 4.9.11.A.1, .2, .5, .8, .9, .11 are applicable.
a. 4.9.11.A.1. – the setback of the facility, including wells or equipment, shall be 20’ from any adjacent residential zone.
b. 4.9.11.A.2. – Where a facility is not enclosed within a building, the surrounding screen shall be used as the building wall for the purpose of setbacks.
c. 4.9.11.A.5. – The use shall not have any service or storage yards.
d. 4.9.11.A.8. – Any building housing such facility shall be in keeping with the character of the zone in which it is located. The Design Review Board (DRB) shall review all applications and make recommendations to the Zoning Examiner.
e. 4.9.11.A.9. – The use shall be located wholly within an enclosed building or within an area enclosed on all sides with a masonry wall or compact evergreen hedge, not less than 6’ nor more than 10’ in height.
f. 4.9.11.A.11. – The use shall be limited to water pumping and storage facilities, telephone exchanges, and power substations with an input voltage of no greater than 138 kilovolts.
3. The parking requirement for the proposed use is 1 space per 500 SF GFA, with a minimum of 2 spaces per facility.
4. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards.

If you have any questions, please contact me at Loran.Shamis@tucsonaz.gov.
05/26/2021 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Completed 230 - 250 pm - T21PRE0118 - 2801 E WAVERLY ST - Site Well B-043B, Tucson Water

1. Tucson Water's New Area Development section has no objections to the proposed development.

2. Any questions, comments or concerns about these comments may be directed to:
Tim Rowe, P.E., Civil Engineer
Tucson Water, New Development Section
310 W. Alameda St.
P.O. Box 27210
Tucson, AZ 85726-7210
(520) 837-2106
05/26/2021 SBLOOD1 ENGINEERING REVIEW Completed 1. This site is within a flood hazard area and will require a floodplain use permit.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov