Plan Number: T21PRE0109
Parcel: Unknown

Address:
2020 W PRINCE RD

Review Status: Completed

Review Details: PREAPPLICATION LABELS

Plan Number - T21PRE0109
Review Name: PREAPPLICATION LABELS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2021 LOREN MAKUS ENGINEERING REVIEW Completed 1. Site is in critical basin. Fifteen per cent reduction in peak discharge is required. Existing conditions including existing retention and detention basins can be taken into consideration.
2. Below grade retention allowed if criteria are met.
3. Disposal of retained and detained volumes must be completed within 24 hours.
4. Pima County Detention/Retention manual should be used with modifications as adopted.
5. Ruthrauff Basin Study information is available from RFCD.
6. The lowest adjacent grade for the new building must be above the adjacent BFE.
7. Maximum depth in parking areas must not exceed 12 inches.
8. Drainage solutions must be on site.
05/12/2021 MROSS2 COT NON-DSD FIRE Completed Fire sprinkler system and fire alarm system modifications require a deferred submital through TFD.


Michael Ross
520-837-7082
Michael.Ross2@Tucsonaz.gov
05/19/2021 AWARNER1 LANDSCAPE REVIEW Completed CDRC TRANSMITTAL

TO: Planning and Development Services Department, Plans Coordination
FROM: Anne Warner, RLA
PDSD Landscape/NPPO Review
PROJECT: 2020 W. Prince Rd, Sam Levitz Expansion
T21PRE0109

TRANSMITTAL DATE: May 19, 2021


UDC Article 7.6 Landscaping and Screening
The Unified Development Code (UDC) requires all new development or an expansion of greater than 25% of an existing development submit a landscape plan, UDC 7.6.2. Preparation of the landscape plan shall adhere to UDC 7.6.4. and Administrative Manual 2-10.


UDC Article 7.7. Native Plant Preservation
An approved Native Plant Preservation Plan Sections 7.7.4 is required or a request for an exception from the Native Plant Preservation requirements in accordance with Sections 7.7.3.D.3 & .4 of the Unified Development Code (UDC) is required prior to Grading Plan approval.


UDC Technical Standards Manual – Section 4-01.0.0. Commercial Rainwater Harvesting and Section 5-01.0.0 Landscaping and Screening


If you have any questions about this transmittal, Contact Anne Warner at (520) 837-4969 or by email anne.warner@tucsonaz.gov
05/19/2021 JVWINKL1 COT NON-DSD TRAFFIC Completed T21PRE0109

1) Assuming this project does not result in a cumulative site expansion greater than 25%
2) New 5' wide sidewalk (where non currently exists) along melody ln
3) What is the semi-truck ingress/egress path for this site? Confirm that there is sufficient maneuvering space for semi-trucks exiting onto prince rd
4) Refer to Access Management Guidelines. 5.12 Truck Loading Area. Truck loading areas should be designed to minimize conflict with on-site traffic and circulation. Drop-off/loading areas should not be located where they will have an effect on traffic operations on the adjoining roadway

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
05/19/2021 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Passed 210 - 230 pm - T21PRE0109 - 2020 W PRINCE RD - SiteGradingSwppp - Sam's Warehouse expansion

1. This project is not in an area served by Tucson Water. Please contact the Flowing Wells Irrigation District with any questions you may have about providing drinking water to this proposed development.

2. Any questions, comments or concerns about these comments may be directed to:
Tim Rowe, P.E., Civil Engineer
Tucson Water, New Development Section
310 W. Alameda St.
P.O. Box 27210
Tucson, AZ 85726-7210
(520) 837-2106
05/20/2021 NMARTEL1 ZONING REVIEW Completed CDRC Thursday Pre-Submittal Transmittal
PDSD Zoning Review
FROM: Nicholas Martell, Planner
PROJECT: Thursday Pre-submittal meeting - T21PRE0109
Address: 2020 W Prince, Parcel: 10610005D
Zoning: I-1
Existing Use: Commercial Storage, Retail Trade, Administrative and Professional Office
Proposed Use: Commercial Storage, Retail Trade, Administrative and Professional Office
TRANSMITTAL DATE: May 20, 2021

COMMENTS:
1. Development must comply with the Administrative Manual Section 2-06 - Development Package.
2. More information is needed to calculate the required parking. If the cumulative floor area results in a 25% or greater expansion, full code compliance must be met. More information regarding the exact use of the proposed expansion will also be required. (7.4.3 UDC)
3. Show bike parking per table 7.4.8-1 of the UDC
4. Ensure access standards found in section 7.8 of the UDC and sections 7-01.0.0 and 10-01.0.0 of the Technical Standards Manual are met. Sidewalks along Weymouth St. and Melody Ln. may be required.
5. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards.

If you have any questions about this transmittal, contact me at Nicholas.Martell@tucsonaz.gov