Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Plan Number: T21PRE0091
Parcel: Unknown

Address:
167 S LINDA AV

Review Status: Completed

Review Details: PREAPPLICATION LABELS

Plan Number - T21PRE0091
Review Name: PREAPPLICATION LABELS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2021 LOREN MAKUS ENGINEERING REVIEW Completed T21PRE0091
1. Site is in area removed from SFHA by LOMR. Development must be consistent with the LOMR to maintain the removal.
2. Coordinate with Pima County RFCD for impact to the Loop and Santa Cruz River facilities.
3. Show solid waste collection and service locations. Provide waste stream calculations.
4. Maximize water harvesting.
5. Show required retention and detention.
05/04/2021 MROSS2 COT NON-DSD FIRE Completed 1.Automatic fire sprinkler system and fire alarm system will be required.
2.Buildings over 30' tall require an approved aerial fire apparatus access road per 2018 IFC section D105
3. A fire department access road shall extend to within 150 feet of all exterior portions of the buidling.
4. the building will need to be tested to determine the need for Emergency Responder Radio Coverage.
5.A building with an occupied floor located more than 75 feet above the lowest level of fire department vehicle access will be classified as a High Rise building and must meet all code applicable to a high rise building.


Michael Ross
520-837-7082
Michael.Ross2@tucsonaz.gov
05/04/2021 MGAYOSS1 DESIGN PROFESSIONAL REVIEW Completed From: Richard Fe Tom, AIA, Design Professional
Sent: Tuesday, May 4, 2021 12:56 PM
Subject: T21PRE0091 - IID-21-02 - 167 S Linda Av - Bautista Mixed Use Presub

The owner needs to present the requirements per the IID for evaluation. It looks to be pretty similar to the other buildings within the Mercado. I would advocate for the building/site to promote larger pedestrian opportunities for the Mercado and neighborhood beyond. Below are some of the major items from sections in the UDC which seemed to be most apparently applicable:
Required IID Review for following
Rio Nuevo Area (UDC 5.12.7)
Downtown Core (UDC 5.12.10)
Downtown Infill Incentive District (UDC 5.12.8)
Applicant shall prepare IID package to address design requirements for the above districts.
Commercial spaces vs. private residential spaces. Identified architecturally and with pedestrian routes, signage.
Will there be private vs public common courtyards? How are they identified?
Consider vehicular traffic & bicycle/pedestrian traffic and how they should be separate per the UDC.
Project should promote, maintain neighborhood linkages (physical & visual)
Include architectural elements, especially on the first two floors. Provide visibility at the first floor.
Outdoor plaza, courtyards shall accommodate multiple uses.
Provide pedestrian shade per requirement.
05/05/2021 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Reqs Change 300 - 345 pm - T21PRE0091 - 167 S LINDA AV - SiteGradingIIDFloodplain Bautista Plaza

1. A water master plan for this project will need to be submitted to Tucson Water's New Development section for review and approval. During the master water planning of this project, please plan on looping the on-site water mains to two different points in Tucson Water's existing water distribution system as required by Section 8-06.4.2.A of Tucson Water's Design Manual to meet water quality and fire flow requirements, or explaining what legal and/or technical reasons prevent such looping.

2. The new water lines will need to be located within public or private streets to the maximum extent practicable. Where this is not practicable, the new water lines will need to be centered within water line easements that lie on smallest number of private lands possible and are a minimum of 15' wide.

3. The Fire Department's fire flow requirements will also need to be shown on the water master plan.

4. Upon approval of the water master plan, a detailed water design plan for the new water lines will need to be submitted to Tucson Water's New Development section for review and approval.

5. The owner of the property will need to enter into a Construction Agreement with Tucson Water regarding the new water main before water line construction may begin.

6. Any questions, comments or concerns about these comments may be directed to:

Tim Rowe, P.E., Civil Engineer
Tucson Water, New Development Section
310 W. Alameda St., P.O. Box 27210
Tucson, AZ 85726-7210, (520) 837-2106
05/05/2021 SBEASLE1 COT NON-DSD ENVIRONMENTAL SERVICES Denied E-mail from: Andy Vera, Andy.Vera@TucsonAz.gov
To: CDRC
Wed 5/5/2021 8:27 AM

Review comments for T21PRE0091 - 167 S LINDA AV - Site/Grading/IID/Floodplain: Bautista Plaza.

ES denies proposed submittal.

Refer to TSM 8-01.0.0.

Must include complete detail and drawings of all solid waste disposal and collection provisions, 8-01.4.0.

Include a general note which identifies proposed service type in relation to waste stream calculations, 8-01.5.0 & 8-01.8.0.

Please contact me if you have any questions regarding this review.
Sincerely,
Andy Vera

City of Tucson -Environmental Services
Accounts Representative Supervisor
(520) 837-3798
05/06/2021 JVWINKL1 COT NON-DSD TRAFFIC Completed T21PRE0091

1) An updated traffic impact analysis will be required for this development to determine to determine if any local improvements are need in the ROW. Refer to section 6.3.2 of the City of Tucson Access Management Guidelines

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
05/11/2021 SBEASLE1 ZONING REVIEW Needs Review
05/11/2021 FRANK PODGORSKI HPZ ADVISORY BOARD HPZ ADVISORY BOARD DATE Needs Review
05/11/2021 SBEASLE1 LANDSCAPE REVIEW Needs Review