Plan Review Detail
Review Status: Completed
Review Details: PREAPPLICATION LABELS
Plan Number - T21PRE0076
Review Name: PREAPPLICATION LABELS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/31/2021 | ANDREW CONNOR | LANDSCAPE | REVIEW | Completed | Show compliance with landscaping and screening requirements by locations, material descriptions, and dimensions. Specific plant or hardscape material shall be detailed on a landscape plan. A detailed landscape plan is required. In accordance with Section 2-10.0.0, Landscape Plan Requirements. |
| 04/08/2021 | LOREN MAKUS | ENGINEERING | REVIEW | Completed | T21PRE0076 1. The site is in a balanced basin. Since the current development was constructed after 1984, balanced basin detention and 5-year threshold is required. 2. Maximize water harvesting. 3. Show solid waste storage and collection location. 4. If DP is submitted after June 1, it must comply with recently adopted retention/detention manual. 5. Preliminary site plan shows fuel tanks in existing retention detention basin. Show how capacity of basin will be retained and how stormwater contamination will be prevented. |
| 04/12/2021 | MROSS2 | COT NON-DSD | FIRE | Completed | An 'FDC' is noted on the plan. If a sprinkler system will be installed note that on the plan along with the location of the underground fire service water line. Michael Ross 520-837-7082 Michael.Ross2@tucsonaz.gov |
| 04/14/2021 | SBEASLE1 | TUCSON WATER NEW AREA DEVELOPMENT | REVIEW | Completed | 200 - 230 pm - T21PRE0076 - 4733 S CAMPBELL AV - Site Fry's 1. Water is supplied to this parcel via an existing 6" PVC dead-end, water main on the east side of Campbell Avenue. 2. A Fire Department Connection is noted on the plan. If a fire suppression sprinkler system is to be installed at this location, please contact Tucson Water, when the automatic sprinkler system demand (including hose stream allowance) is known, and request a verification that Tucson Water's existing water lines can supply the necessary amount of water. 3. Any questions, comments or concerns about these comments may be directed to: Tim Rowe, P.E., Civil Engineer Tucson Water, New Development Section 310 W. Alameda St. P.O. Box 27210 Tucson, AZ 85726-7210 (520) 837-2106 |
| 04/15/2021 | JVWINKL1 | COT NON-DSD | TRAFFIC | Completed | T21PRE0076 1) Existing sidewalk along S Campbell Ave will need to be brought into ADA compliance. If sidewalk is less then 4' wide and out of compliance, it will need to be replaced with a minimum 6' wide sidewalk. This includes new curb access ramps. 2) Radius of curb return off of S Campbell Av will need to be minimum of 25' John Van Winkle, P.E. John.VanWinkle@tucsonaz.gov |
| 04/15/2021 | NMARTEL1 | ZONING | REVIEW | Completed | CDRC Thursday Pre-Submittal Transmittal PDSD Zoning Review FROM: Nicholas Martell, Planner PROJECT: Thursday Pre-submittal meeting - T21PRE0076 Address: 4733 S Campbell Av, Parcel: 13219102B Zoning: C-2 Existing Use: Automotive, Minor Service and Repair Proposed Use: General Merchandise Sales TRANSMITTAL DATE: April 15, 2021 COMMENTS: 1. Development must comply with the Administrative Manual Section 2-06 - Development Package. 2. General Merchandise Sales is permitted in the C-2 zone with use the use specific standard: 4.9.9.B.1 3. Parking is calculated at 1 space per 300 sq ft GFA. 4. Campbell Avenue is a major street. The setback will be measured from the back of the future curb. 5. Bicycle Parking is required at 2 short term and 2 long term spaces per table 7.4.8-1 of the UDC 6. Ensure access standards found in section 7.8 of the UDC and sections 7-01.0.0 and 10-01.0.0 of the Technical Standards Manual are met. 7. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards. If you have any questions about this transmittal, contact me at Nicholas.Martell@tucsonaz.gov |