Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Plan Number: T21PRE0073
Parcel: Unknown

Review Status: Completed

Review Details: PREAPPLICATION LABELS

Plan Number - T21PRE0073
Review Name: PREAPPLICATION LABELS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2021 ANDREW CONNOR LANDSCAPE REVIEW Completed Show compliance with landscaping and screening requirements by locations, material descriptions, and dimensions. Specific plant or hardscape material shall be detailed on a landscape plan. A detailed landscape plan is required. In accordance with Section 2-10.0.0, Landscape Plan Requirements.
04/08/2021 LOREN MAKUS ENGINEERING REVIEW Completed T21PRE0073
1. This site is not in a balanced or critical basin. If Development Package is submitted after June 1, it will be considered balanced. There can be no increase in discharge in the 2-, 10-, and 100-year events.
2. If the DP is submitted after June 1, 2021, it must comply with the newly adopted retention and detention manual.
3. Maximize water harvesting.
4. Site must comply with Transportation Access Management Guidelines. Driveways must be separated by 80 feet, including driveways on adjacent properties.
5. Curb returns with 25-foot radii are required for the driveways.
6. Show solid waste storage and collection location with maneuverability.
04/13/2021 MROSS2 COT NON-DSD FIRE Completed Fire sprinklers and a fire alarm system will be required.
Buildings over 30 feet in height require an approved aerial fire apparatus access road and not fewer than two means of fire apparatus access, per Appendix D of the 2018 IFC.
Aerial fire access roads shall be a minimum width of 26 feet and shall be located not less than 15 feet and not greater than 30 feet from the building and shall be positioned paralled to one entire side of the building.

There is an access gate noted on the north side of the property. The road that accesses that gate needs to meet the requirements of section 503 and Appendix D of the 2018 IFC.


Michael Ross
520-837-7082
Michael.Ross2@TucsonAZ.gov
04/14/2021 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Completed 130 - 200 pm - T21PRE0073 - 5925 E SPEEDWAY BL - Site Speedway Storage

1. Water is currently supplied to the existing buildings on these parcels via an existing 12" cement asbestos water main (PN 019-1962) on the south side of Speedway Blvd.

2. After a water fixture unit count has been conducted for the project using the 2018 International Plumbing Code, and the fire flow requirements have been established by the local fire authority, please contact Tucson Water's New Services section by sending an e-mail to TW_COMMON@tucsonaz.gov to discuss:
a. Potential points of connection to Tucson Water's existing water distribution system. Please note that hydraulic modeling may need to be performed to verify which potential points of connection have the capacity necessary to serve the proposed development.
b. The number of water service lines, water meters, and meter sizes, necessary to serve this development.
c. The advantages and disadvantages of installing the necessary water meters via Tucson Water's Job Order Contract (JOC) process.

3. Any questions, comments or concerns about these comments may be directed to:

Tim Rowe, P.E., Civil Engineer
Tucson Water, New Development Section
310 W. Alameda St.
P.O. Box 27210
Tucson, AZ 85726-7210
(520) 837-2106
04/15/2021 JVWINKL1 COT NON-DSD TRAFFIC Completed T21PRE0073

1) City of Tucson Access Management requirements need 300' of frontage for every 2 driveway entrances. Frontage is approximately 210 feet. 1 driveway entrance would currently be allowed for new development. Driveway must be 80' away from adjacent property entrances.
2) Per (TSM) section 10-01.3.2.C. At the intersections of streets with other streets or collector or arterial streets with PAALs/Driveways, the curb lines will be connected with a curve having the minimum radius shown in Figure 6, measured at the face of the curb. Proposed driveway to Speedway is to have a 25' radius
3) A new 6' sidewalk will need to be provided along the projects frontage on Speedway

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
04/15/2021 SAMUEL ROGERS ZONING REVIEW Completed CDRC Thursday Pre-Submittal Transmittal
PDSD Zoning Review

FROM: Samuel Rogers, Planner

PROJECT: Thursday Pre-submittal meeting – T21PRE0073
Address: 5925 and 5943 E. Speedway Blvd
Parcel(s): 121-07-0150 & 121-07-0160
Zoning: C-2
Existing Use: Animal Service
Proposed Use: Personal Storage

TRANSMITTAL DATE: 04/15/2021

COMMENTS:
1. Development must comply with the Administrative Manual Section 2-06 - Development Package.
2. The use per the UDC is Personal Storage. As a general note on DP add the use and applicable Use-Specific Standard code references.
3. 4.9.10.C.3 - All walls or doors visible from adjacent streets and residential properties shall be surfaced with a non-reflective material.
4. 4.9.10.C.6 - The facility’s exterior facade visible from adjoining residential properties or street frontage shall be earth tone in color and of masonry, stucco, or similar materials.
5. The required setback to the north is 1.5 the height of the structures adjacent wall, the required setback to the east and west is 0’, and the streetside setback to the south is 21’ or the height of the wall measured from the back of the future curb location. It does not appear the proposal is meeting setback requirements to the north (required setback: 35’ x 1.5 = 52.5’).
6. The future ROW is proposed to be 120’ and is currently 100’. 10’ of ROW will be taken from each side of the street. The plan must reflect the future ROW location.
7. The max height in this zone is 40’.
8. Either direct vehicular access or non-direct vehicular access is allowed with different requirements.
9. Identify door location (i.e. roll up doors, office entrance, etc.) on future plans.
10. 1 parking space per 4,000 sq. ft. GFA is required, if storage units do not have direct vehicular access, and a minimum of 2 spaces for any associated office. No direct vehicle access appears to be proposed, so 10 spaces will be required.
(0 parking spaces are required for storage units, if storage units have direct vehicular access, and a minimum of 2 spaces for any associated office.)
11. 2 short term bicycle spaces will be required.
12. For development without direct vehicular access 1 Type A loading space will be required (Type A: 12 feet by 35 feet).
No loading zones are required personal storage developments with direct vehicular access.
13. Pedestrian connection will be required to Speedway Blvd.
14. Vehicular egress/ingress will not be allowed to the north of the property. Ingress/egress is not allowed on private property unless an access agreement is recorded. Is the emergency access gate only for fire trucks only?
15. A development package (DP) will be required to be issued prior to issuance of any building permits, however building permits can be submitted as risk prior to the DP’s issuance.
16. Submit application for a lot combination to county, accessor confirmation of submitted lot combination form must be submitted prior to the issuance of the development package.
17. Architectural documentation will need to submitted for the demolition permit.
18. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards.

If you have any questions please contact me at Samuel.Rogers@tucsonaz.gov