Plan Number: T21PI00016
Parcel: Unknown

Address:
2730 E DREXEL RD

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T21PI00016
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2022 GARY WITTWER DOT LANDSCAPE REVIEW Reqs Change Landscape Comments:

1. Please extend the seed mix to the sidewalk and the area between sidewalk and curb.
2. Please install 4" PVC sleeves at a 2.5 foot depth under each of the driveways that extend 2" beyond the driveways on each side. Plug ends to prevent backfill dirt from entering pipe.
Thanks,

David

David Marhefka
da’-vid mär-hef’-ka
Landscape Architect
City of Tucson
Department of Transportation and Mobility
(o) 520-837-6618
(m) 520-403-5074
01/12/2022 RLEIGH1 UTILITY CLEARANCES COT STREETS DIVISION Needs Review Submit Utility Notification Receipts for the Utilities listed on the DTM Utility Clearance Letter Which can be found at https://www.tucsonaz.gov/tdot/private-improvement-agreement-guidelines.
01/12/2022 ZELIN CANCHOLA DOT TRAFFIC REVIEW Reqs Change DTM Traffic Engineering:

1. Sheet 4, Keynote 2 should refer to Detail Sheet 3.1.1b - COT uses the 2 runs of Type D RPMs. County uses 3.1.1a

2. Sheet 4, Keynote 3: edge stripe/bike lane stripe should be WS6

3. Sheet 4, Keynote 4: for all the driveways, no need to break the WS6 solid striping. COT keeps solid stripe across driveways. Only break edge stripe at named side streets

Greg Orsini, P.E.
520-837-6617
Gregory.Orsini@tucsonaz.gov
01/12/2022 RICHARD LEIGH PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
01/12/2022 JIM FEMLING DOT STREET MAINTENANCE REVIEW Approved
01/12/2022 ERNIE ENCINAS DOT_ELEC REVIEW Approved
01/12/2022 RICHARD LEIGH DOT ENGINEERING REVIEW Reqs Change January 12, 2022

SUBJECT: Offsite Improvement Plan for Drexel Rd Public Improvements

PROJECT REVIEWER: Richard Leigh, DTM Eng. Review

RESUBMITTAL REQUIRED: TDOT Permit Review Section has reviewed the subject PIA paving plan and does not recommend approval at this time. The following comments need to be addressed and plans revised prior to resubmittal. Please include a response letter addressing the following comments.

1. Address redline comments on plan markups emailed.

If you have any questions, I can be reached at 520-237-8692 or emailed at Richard.Leigh@tucsonaz.gov.
01/12/2022 RICHARD LEIGH PIA COORDINATOR OUT TO CUSTOMER Completed
01/12/2022 RLEIGH1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Needs Review Submit Utility Notification Receipts for the Utilities listed on the DTM Utility Clearance Letter Which can be found at https://www.tucsonaz.gov/tdot/private-improvement-agreement-guidelines.
01/12/2022 RLEIGH1 UTILITY CLEARANCES PC WASTEWATER MGMT Needs Review Submit Utility Notification Receipts for the Utilities listed on the DTM Utility Clearance Letter Which can be found at https://www.tucsonaz.gov/tdot/private-improvement-agreement-guidelines.
01/12/2022 RLEIGH1 UTILITY CLEARANCES QUEST COMMUNICATION Needs Review Submit Utility Notification Receipts for the Utilities listed on the DTM Utility Clearance Letter Which can be found at https://www.tucsonaz.gov/tdot/private-improvement-agreement-guidelines.
01/12/2022 RLEIGH1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Needs Review Submit Utility Notification Receipts for the Utilities listed on the DTM Utility Clearance Letter Which can be found at https://www.tucsonaz.gov/tdot/private-improvement-agreement-guidelines.
01/12/2022 RLEIGH1 UTILITY CLEARANCES COX COMMUNICATION Needs Review Submit Utility Notification Receipts for the Utilities listed on the DTM Utility Clearance Letter Which can be found at https://www.tucsonaz.gov/tdot/private-improvement-agreement-guidelines.
01/12/2022 RLEIGH1 UTILITY CLEARANCES SOUTHWEST GAS CORP Needs Review Submit Utility Notification Receipts for the Utilities listed on the DTM Utility Clearance Letter Which can be found at https://www.tucsonaz.gov/tdot/private-improvement-agreement-guidelines.
01/12/2022 RLEIGH1 UTILITY CLEARANCES EL PASO NATURAL GAS Needs Review Submit Utility Notification Receipts for the Utilities listed on the DTM Utility Clearance Letter Which can be found at https://www.tucsonaz.gov/tdot/private-improvement-agreement-guidelines.
01/12/2022 RLEIGH1 UTILITY CLEARANCES KINDER MORGAN ENERGY Needs Review Submit Utility Notification Receipts for the Utilities listed on the DTM Utility Clearance Letter Which can be found at https://www.tucsonaz.gov/tdot/private-improvement-agreement-guidelines.