Plan Number: T21PI00012
Parcel: Unknown

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T21PI00012
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2021 RICHARD LEIGH PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
10/27/2021 ZELIN CANCHOLA DOT TRAFFIC REVIEW Approved
10/27/2021 RLEIGH1 UTILITY CLEARANCES COT STREETS DIVISION Needs Review
10/27/2021 GARY WITTWER DOT LANDSCAPE REVIEW Approved
10/27/2021 ERNIE ENCINAS DOT_ELEC REVIEW Approved
10/27/2021 JIM FEMLING DOT STREET MAINTENANCE REVIEW Approved
10/27/2021 RICHARD LEIGH DOT ENGINEERING REVIEW Reqs Change John Van Winkle, P.E.
Engineering Manager
Department of Transportation and Mobility
C (520) 429-6116



1) Recordation information must be noted on the cover sheet. Plat must be recorded before submittal of mylars for final approval
2) Add the following “All Drainage Infrastructure, indicated on the plans, is in accordance with the Drainage Report approved by the Planning and Development Services Department”
3) Removed duplicated note 20 on sheet 2, which is shown on note 6 on sheet 1
4) Add the following note “The City shall not be held liable for any errors and/or omissions on these plans. Items not meeting City Standards shall be repaired/replaced at no cost to the City”
5) Add the following note “The Engineer of Record shall submit to the City for review any changes to the approved plans prior to construction. Additionally, the Engineer of Record shall certify all changes meeting all applicable standards, codes, and ordinances.
6) Add the following note “Floodplain Use Permit No,______ has been issued by Planning and Development Services Department for work impacting City and FEMA Floodplains.
7) Sheets 3-4 indicate which roadway cross section is being provided, A or B shown on sheet 7.
8) Sheets 3 and 4, keynote 6, references detail E6. This should be detail E7?
9) Add T21PI00012 to plans as needed
10) Add Plan number I-2021-012 to all sheets.
10/27/2021 RICHARD LEIGH PIA COORDINATOR OUT TO CUSTOMER Completed
10/27/2021 RLEIGH1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Needs Review
10/27/2021 RLEIGH1 UTILITY CLEARANCES PC WASTEWATER MGMT Needs Review
10/27/2021 RLEIGH1 UTILITY CLEARANCES QUEST COMMUNICATION Needs Review
10/27/2021 RLEIGH1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Needs Review
10/27/2021 RLEIGH1 UTILITY CLEARANCES COX COMMUNICATION Needs Review
10/27/2021 RLEIGH1 UTILITY CLEARANCES SOUTHWEST GAS CORP Needs Review
10/27/2021 RLEIGH1 UTILITY CLEARANCES EL PASO NATURAL GAS Needs Review
10/27/2021 RLEIGH1 UTILITY CLEARANCES KINDER MORGAN ENERGY Needs Review