Plan Number: T21PI00006
Parcel: Unknown

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T21PI00006
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2021 JIM FEMLING DOT STREET MAINTENANCE REVIEW Approved
05/13/2021 RLEIGH1 UTILITY CLEARANCES COT STREETS DIVISION Needs Review
05/13/2021 ZELIN CANCHOLA DOT TRAFFIC REVIEW Reqs Change Reviewer:
Greg Orsini, P.E.
Gregory.Orsini@tucsonaz.gov
(520) 268-5036



1. Sheet 9, Signing Note 1 and Striping Note 1 refer to old pavement marking and signing manuals. As of December 2020, the joint PC/COT Signing and Pavement Marking manuals have now been combined, so wherever referenced, we should probably refer to the new joint "PC/COT Signing & Pavement Marking Manual" (Typical). If needed, the consultant can refer to the new manual at https://webcms.pima.gov/UserFiles/Servers/Server_6/File/Government/Transportation/Roadway%20Design/FINAL-Pima-County_City-of-Tucson-Signing-and-Pavement-Marking-Manual-2020-First-Edition_linking_nocomments-12_21.pdf

2. Sheet 9, Signing Note 7: Hard to tell if the note refers to Type II sheeting or Type XI sheeting, but it should be Type XI (eleven)

3. Sheet 9, Striping Notes 6 and 7 Need to be replaced. Should be like the following (taken from another Rick Engineering plan set):

6. ALL FINAL LONGITUDINAL STRIPING SHALL BE 90 MIL (0.090”) THICK THERMOPLASTIC REFLECTORIZED STRIPING PLACED OVER THE TEMPORARY STRIPING WITHIN 14 TO 30 CALENDAR DAYS AFTER COMPLETION OF THE FINAL PAVEMENT SURFACE.OR AS DIRECTED BY THE TRAFFIC ENGINEER. ALL OTHER MARKINGS SHALL BE APPLIED AT THE SAME TIME. TEMPORARY STRIPING SHALL BE PAINT.

7. ALL FINAL TRANSVERSE MARKINGS SHALL BE 90 MIL (0.090”) THICK THERMOPLASTIC STRIPING. ALL PAVEMENT ARROWS AND LEGENDS SHALL BE 90 MIL (0.090”) THICK THERMOPLASTIC PAVEMENT MARKINGS. EXTRUDED THERMOPLASTIC OR PREFORMED APPLICATIONS MAY BE USED IF APPROVED BY THE TRAFFIC ENGINEER.

4. Sheet 9, STOP signs are not necessary at "T" intersections (Sta 10+60, Sta 21+70, Sta 35+90)
05/13/2021 ERNIE ENCINAS DOT_ELEC REVIEW Approved
05/13/2021 RLEIGH1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Needs Review
05/13/2021 RLEIGH1 UTILITY CLEARANCES PC WASTEWATER MGMT Needs Review
05/13/2021 RLEIGH1 UTILITY CLEARANCES QUEST COMMUNICATION Needs Review
05/13/2021 RLEIGH1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Needs Review
05/13/2021 RLEIGH1 UTILITY CLEARANCES COX COMMUNICATION Needs Review
05/13/2021 RLEIGH1 UTILITY CLEARANCES SOUTHWEST GAS CORP Needs Review
05/13/2021 RLEIGH1 UTILITY CLEARANCES EL PASO NATURAL GAS Needs Review
05/13/2021 RLEIGH1 UTILITY CLEARANCES KINDER MORGAN ENERGY Needs Review
05/14/2021 GARY WITTWER DOT LANDSCAPE REVIEW Approved
05/28/2021 RICHARD LEIGH PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
05/28/2021 RICHARD LEIGH DOT ENGINEERING REVIEW Reqs Change RESUBMITTAL REQUIRED: TDOT Permit Review Section has reviewed the subject PIA paving plan and does not recommend approval at this time. The following comments need to be addressed and plans revised prior to resubmittal. Please include a response letter addressing the following comments.


1. Add the plan number “I-2021-005” in the title block of each sheet.

2. Add PIA activity number “T21PI00006” on coversheet.

3. Add the subdivision Development Plan number on coversheet.

4. Label all roadways with platted street names.

5. The proposed storm drain roadway crossings for this project will have to be private and in private drainage easements. Contact COT Dept. of Transportation & Mobility Real Estate division for obtain easements.

6. Sheet 1: Revise reference to Signing and Striping Manual to reference to the current Pima County / City of Tucson Signing & Pavement Marking Manual (2020 Edition)

7. Sheet 2 through 11: Remove signatory titles from title blocks on sheets 2 through 11.

8. Sheet 3: Clearly demonstrate how the drainage from Valencia Crossing Dr will be addressed north of Sta. 55+00, Valencia Crossing Dr.

9. Refer to redline drawings for additional comments and comment details.

If you have any questions, I can be reached at 520-237-8692 or emailed at Richard.Leigh@tucsonaz.gov.
05/28/2021 RICHARD LEIGH PIA COORDINATOR OUT TO CUSTOMER Completed