Plan Number: T21PI00004
Parcel: Unknown

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T21PI00004
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/09/2021 GARY WITTWER DOT LANDSCAPE REVIEW Reqs Change DTM Landscape:

Place the following notes on the plans as they do not appear on the Development Package Plans. Comply with all notes.

City of Tucson
Department of Transportation and Mobility
Standard Notes for Planting in ROW

1. It is the owner’s responsibility to keep the Sight Visibility Triangles (SVT), and the pedestrian access area clear of vegetation at all times, per Unified Development Code (UDC) Technical Standards Manual Section 10.
2. It is the owner responsibility to keep a 5’ wide by 7’ tall clear pedestrian access open across the entire property.
3. It is the owner responsible to keep vegetation from growing past the curb line clear, and keep a 15’ high clear zone over the travel lane.
4. Final plant locations must be in compliance with all utility setback requirements.
5. The owner understands that if the City of Tucson Transportation Department or any utility company needs to work within the ROW in the landscaped area, plants and irrigation may be destroyed without replacement or repair.
6. The owner takes full liability for this landscape and irrigation, and any damage to roadway, sidewalk and utilities.
7. The only private irrigation equipment that is allowed within the ROW are lateral lines, tubing and emitters that are not under constant pressure. All other equipment must be on private property. (excluding water meter)
8. Contractor to obtain a Right Of Way permit prior to construction within the right-of-way.


City of Tucson, Department of Transportation and Mobility
Requirements for placement of Private Irrigation Facilities Roadway Crossings within the Public Rights-of-Way
1. Private irrigation facilities roadway crossings will only be permitted in residential roadways and NOT permitted in arterial or collector roadways.
2. Lateral lines under constant pressure shall not be permitted in the public rights-of-way.
3. The HOA will register private irrigation facilities placed in the public rights-of-way with Arizona 811and become an Arizona 811 Blue Stake Inc. member.
4. Minimize the number of roadway crossings.
5. Sleeves must be in a recorded easement (easement width is dependent on what is needed for installation and/or repairs). To the extent possible, the easements should be created at the time of development/platting.
6. Irrigation lines shall be placed in ductile iron sleeves.
7. Sleeve should extend beyond the right-of-way (into private property), unless otherwise approved by DOT&M.
8. HDPE continuous line (no joints under the pavement)
9. Irrigation lines shall have a minimum of thirty (30) inches of cover.
10. Detectable marking tape shall be installed.
11. Curb shall be marked/stamped with “IS” (Irrigation System) and/or placard at back of curb.


Thanks,

David

David Marhefka
da’-vid mär-hef’-ka
Landscape Architect
City of Tucson
Department of Transportation and Mobility
(o) 520-837-6618
(m) 520-403-5074
03/09/2021 RLEIGH1 UTILITY CLEARANCES COT STREETS DIVISION Completed
03/09/2021 ZELIN CANCHOLA DOT TRAFFIC REVIEW Reqs Change Traffic Engineering

Reviewer:
Greg Orsini P.E.
Greg.Orsini@tucsonaz.gov
(520) 837-6617 Office
(520) 268-5036 Cell

1- Sheet 4: No need for STOP sign at this intersection.
2- Sheet 5 & 8/General: Please install street name signs at intersections.
3- Sheet 7: STOP signs not needed for "T" intersections.
03/09/2021 RICHARD LEIGH PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
03/09/2021 JIM FEMLING DOT STREET MAINTENANCE REVIEW Approved
03/09/2021 ERNIE ENCINAS DOT_ELEC REVIEW Approved
03/09/2021 RICHARD LEIGH DOT ENGINEERING REVIEW Reqs Change March 9, 2021

SUBJECT: La Estancia Phase II, Parcel 2 Paving Plans

PROJECT REVIEWER: Richard Leigh, DTM Eng. Review

RESUBMITTAL REQUIRED: TDOT Permit Review Section has reviewed the subject PIA paving plan and does not recommend approval at this time. The following comments need to be addressed and plans revised prior to resubmittal. Please include a response letter addressing the following comments.


1. Add the plan number “I-2021-010” in the title block of each sheet.

2. Add PIA activity number “T21PI00004” on coversheet.

3. Sheets 3: Revise scupper detail to indicate placement of barricade railing along the back of the scupper.

4. Sheet 5: Indicate placement of a midblock ramps on Paseo Berceo between Via De Dos Abuelas and Camino Alma Vieja.

5. The City of Tucson does not require STOP signs at T intersections, see PCDOT/COT Signing and Marking Standards Sheet 8.15. Revise plan set to reflect this.

6. Indicate placement of street name signs at roadway knuckles.

7. Indicate placement of No Parking signs at frequency of approximately 100’, along the parking restriction zones.

If you have any questions, I can be reached at 520-237-8692 or emailed at Richard.Leigh@tucsonaz.gov.
03/09/2021 RICHARD LEIGH PIA COORDINATOR OUT TO CUSTOMER Completed
03/09/2021 RLEIGH1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Completed
03/09/2021 RLEIGH1 UTILITY CLEARANCES PC WASTEWATER MGMT Completed
03/09/2021 RLEIGH1 UTILITY CLEARANCES QUEST COMMUNICATION Completed
03/09/2021 RLEIGH1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Completed
03/09/2021 RLEIGH1 UTILITY CLEARANCES COX COMMUNICATION Completed
03/09/2021 RLEIGH1 UTILITY CLEARANCES SOUTHWEST GAS CORP Needs Review
03/09/2021 RLEIGH1 UTILITY CLEARANCES EL PASO NATURAL GAS Completed
03/09/2021 RLEIGH1 UTILITY CLEARANCES KINDER MORGAN ENERGY Completed