01/20/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1; Code Analysis: This table indicates '200 SF/person', then indicates an occupant load of 10. The structure has 1088 SF, which allows 1088/200 = 6 occupants maximum. Please verify.
2. Sheet A1; Project Data: The area calculations in this table indicate bedrooms of 141 SF, 121.5 SF, and 113.7 SF. The SF required in bedrooms is 80 SF for one occupant, and 120 SF for two occupants. Using that guideline, the maximum occupant capacity is six. Please verify.
3. General: Please provide written responses to all review comments.
01/25/2022 STEVE SHIELDS ZONING REVIEW Approved