Permit Number - T21OT00899
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change Previous Comment 1. Drawing #1: Please provide a Code Analysis on this sheet per the 2018 IBC Section 310. Include applicable codes, building square footage, construction type, occupancy classification, and occupant load.
Previous Comment 2. Drawing #1: Per the IBC Section 903.2.8, an automatic sprinkler system shall be provided with a Group R fire area. Please indicate on this sheet.
Previous Comment 3. Drawing #1: Per the IBC Section 1030, emergency escape and rescue openings shall be provided in Group R-3 and R-4 occupancies. Please indicate the emergency escape and rescue openings requirements on this sheet, and verify this project meets those requirements.
Previous Comment 4. Drawing #1: Verify on this sheet accessible routes (Section 1104), accessible entrances (Section 1105), and dwelling units (Section 1107) meet the accessibility requirements for this occupancy classification.
5. General: Please provide written responses to all review comments.