Permit Number: T21OT00899
Parcel: 133480920

Review Status: Completed

Review Details: C OF O

Permit Number - T21OT00899
Review Name: C OF O
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2022 STEVE SHIELDS ZONING REVIEW Approved
01/02/2022 SSHIELD1 ENGINEERING REVIEW Passed
12/28/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Drawing #1: Please provide a Code Analysis on this sheet per the 2018 IBC Section 310. Include applicable codes, building square footage, construction type, occupancy classification, and occupant load.
2. Drawing #1: Per the IBC Section 903.2.8, an automatic sprinkler system shall be provided with a Group R fire area. Please indicate on this sheet.
3. Drawing #1: Per the IBC Section 1030, emergency escape and rescue openings shall be provided in Group R-3 and R-4 occupancies. Please indicate the emergency escape and rescue openings requirements on this sheet, and verify this project meets those requirements.
4. Drawing #1: Verify on this sheet accessible routes (Section 1104), accessible entrances (Section 1105), and dwelling units (Section 1107) meet the accessibility requirements for this occupancy classification.
5. General: Please provide written responses to all review comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/03/2022 NGARCIA3 OUT TO CUSTOMER Completed