Review Details: C OF O

Permit Number - T21OT00551
Review Name: C OF O
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2021 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Reqs Change 1. Please provide a complete code analysis for the proposed use.
2. The plan requires a stamp from an architect registered in the State of Arizona
08/20/2021 STEVE SHIELDS ZONING REVIEW Approved
08/30/2021 JPEELDA1 FIRE REVIEW Reqs Change Drawings shall be drawn by a registered architect
Plans shall have a code analysis
Plans shall reference codes used
Plans shall show changes made to the structure and interior
Plans shall show if the building has a fire alarm and or fire sprinklers
Plans shall show occupant type and load