09/23/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change No responses were received from the first review comments. Please provide.
1. Sheet A-1; Project Summary; Area Calculations: This summary indicates an addition of 782 SF. Are the exterior walls of Bedrooms #3, 4, and 5 new on this project? Please indicate a Permit Number on this sheet if a previous permit was submitted and issued. If this project includes the addition of new square footage, complete architectural, structural, mechanical, plumbing, and electrical drawings and calculations are required. A Schedule of Drawings on this sheet indicates those drawings are included in this submittal. Please clarify on this sheet the new project summary.
2. Sheet A-1; Site Plan: There are several note references on this plan, but no notes are listed. Please provide.
3. Sheet A-1; Applicable Codes: Please revise the National Electric Code to the 2017 Edition.
4. Sheet A-1; Building Code: The IBC Section 903.2.8 requires buildings with a Group R fire area shall have an automatic sprinkler system. Please indicate the automatic sprinkler system requirement on this sheet.
5. Sheet A-1; Building Code: The Allowable Area indicates unlimited SF. Please revise this per the IBC Table 506.2.
6. Sheet A-1; Code Analysis: The principle use is listed as R-3 Congregate Living. Please revise this to R-4 Assisted Living.
7. Sheet A-1; Code Analysis: The Parking Requirements indicate this is not a change of use. Please clarify that with the previous use listed.
8. Sheet A-1; Floor Plan Keynotes: Note 3 indicates fire rated wall. Fire partitions per the IBC Section 708 would be required. Provide a detail of these walls, indicating the fire resistance rating and a U.L. Number for that wall assembly.
9. General: Please provide written responses and clarifications to all review comments.