Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21OT00510
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/23/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | No responses were received from the first review comments. Please provide. 1. Sheet A-1; Project Summary; Area Calculations: This summary indicates an addition of 782 SF. Are the exterior walls of Bedrooms #3, 4, and 5 new on this project? Please indicate a Permit Number on this sheet if a previous permit was submitted and issued. If this project includes the addition of new square footage, complete architectural, structural, mechanical, plumbing, and electrical drawings and calculations are required. A Schedule of Drawings on this sheet indicates those drawings are included in this submittal. Please clarify on this sheet the new project summary. 2. Sheet A-1; Site Plan: There are several note references on this plan, but no notes are listed. Please provide. 3. Sheet A-1; Applicable Codes: Please revise the National Electric Code to the 2017 Edition. 4. Sheet A-1; Building Code: The IBC Section 903.2.8 requires buildings with a Group R fire area shall have an automatic sprinkler system. Please indicate the automatic sprinkler system requirement on this sheet. 5. Sheet A-1; Building Code: The Allowable Area indicates unlimited SF. Please revise this per the IBC Table 506.2. 6. Sheet A-1; Code Analysis: The principle use is listed as R-3 Congregate Living. Please revise this to R-4 Assisted Living. 7. Sheet A-1; Code Analysis: The Parking Requirements indicate this is not a change of use. Please clarify that with the previous use listed. 8. Sheet A-1; Floor Plan Keynotes: Note 3 indicates fire rated wall. Fire partitions per the IBC Section 708 would be required. Provide a detail of these walls, indicating the fire resistance rating and a U.L. Number for that wall assembly. 9. General: Please provide written responses and clarifications to all review comments. |