Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21OT00302
Parcel: 11450023B

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T21OT00302
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2021 LOREN MAKUS ENGINEERING REVIEW Reqs Change T21OT00302 - Floodplain Use Permit
1. Fahringer Wash is a WASH watercourse. The use of concrete in the channel is not allowed. Provide an alternative such as gabion baskets.
2. Add to the maintenance provisions that the owners will ensure the hinged flip gates will be inspected and maintained to ensure continued operation.
T21BU00179 - Fence Permit
1. Show how the fence is consistent with the report from Chris Rod PE of JE Fuller. Mr. Rod or his authorized representative must certify the plans are consistent with his report.
2. Show in specific detail the location of the gate and drainage openings. The plan must show how the gate relates to existing conditions on adjacent properties.
3. Show how the property owners will have access to the outside of the drainage opening to keep them clear from debris.
4. Show any required changes to the ground necessitated by the modifications to the fence. A grading permit or revision to the previous grading permit may be required.
5. The site plan for the pool permit, T19CM06066, shows a fence in close proximity to the pool. This fence must be shown on the plans and provided as the required barrier for the pool.