Permit Review Detail
Review Status: Completed
Review Details: C OF O
Permit Number - T21OT00160
Review Name: C OF O
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/08/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. General: It appears from the submittal documents this is a Retail Occupancy Classification (M), and the previous Classification was a Business (B). Please verify. That would make this a change of use, which requires the services of a registered design professional (architect) to produce a submittal set of drawings. These drawings must include an aproved site plan (you have that in this submittal, Sheet G1), a building plan (you have that in this submittal, Sheet A1), and a new Code Analysis (this will replace the Code Review on Sheet G1). The architect will provide that information along with Plumbing Fixture Calculations, Accessibility issues, Egress/Exiting, etc. per the 2018 International Existing Building Code, and submit those documents for a permit. |
04/13/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved |