Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/10/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The provided specifications for the plumbing fixtures are inadequate for evaluation of some of the fixtures (e.g. the lab sink with emergency eyewash and the emergency shower). Reference: Section 107.2.1, IBC 2018. [Initial comment: Provide specifications for the new plumbing fixtures. Reference: Sections 303.4 and 402, IPC 2018.]
2. A ¾" supply line for the emergency shower is not sufficient. The Haws model 8100 emergency shower, for example, requires a minimum 1-1/4" supply line and 30-90 PSI flowing water pressure for proper operation (see https://www.hawsco.com/wp-content/uploads/2020/07/8100.pdf). Provide the specification for the emergency shower upon which you are basing your design and show that the installation will comply with the manufacturer's instructions. [Initial comment: Clarify the installation of the emergency shower. The showers typically flow 20 to 40 GPM and a ½" water supply will be inadequate. Reference: Section 303.2, IPC 2018.]
03/23/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved