Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2022 SBLOOD1 ENGINEERING REVIEW Passed
01/09/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/13/2022 ROBERT SHERRY WATER REVIEW Completed
01/13/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide specifications for the new plumbing fixtures. Reference: Sections 303.4 and 402, IPC 2018.
2. The replacement faucets for the lavatory shall be metering faucets. The metering faucets shall dispense a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds for accessibility. Reference: Section 412.11, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1
3. Clarify the installation of the emergency shower. The showers typically flow 20 to 40 GPM and a ½" water supply will be inadequate. Reference: Section 303.2, IPC 2018.
01/19/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Coordinate the heat pump unit numbers in the outdoor air calculation chart with the heat pump schedule and mechanical floor plan. Reference: Section 107.2.1, IBC 2018.
01/24/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1 . Provide complete electrical plans sealed by an Electrical Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.

2. Locate the electrical service equipment on the power plans or electrical site plan. And provide compliance with NEC 230.2.

3. Where are the electrical service meters located at the new electrical service?

4. What is the size and types of the grounding electrode conductors for the electrical service include water,gas, building steel.

5. Provide compliance for service(s) grounding per NEC art 250.58.

6. Identify what is new and what is existing on the power and lighting Plan.

7. Provide a complete luminaire schedule.

8. Show the locations of all the mechanical equipment and circuit, panel designations on the plans.

Provide electrical design and calculations performed by an Electrical Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work.

Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements
01/25/2022 STEVE SHIELDS ZONING REVIEW Approved
01/25/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/25/2022 JPEELDA1 FIRE REVIEW Approved