Permit Number: T21CM09912
Parcel: Unknown

Address:
519 S RUSSELL AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM09912
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM09912
519 S Russell Ave – HC-3
2nd Dwelling Unit (1st Review)


TRANSMITTAL: January 12, 2022
COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8).

This site is located in the HC-3 zone (UDC 4.7.22).

1. Historic review required for addition of 2nd dwelling unit.

2. Per UDC TABLE 6.3-4.A: DIMENSIONAL STANDARDS FOR THE C-1, C-2, C-3, OCR-1, & OCR-2 ZONES, HC-3 Zone, Res Use to Nonres Zone the required perimeter yard setbacks to the north, south and east property line is 0’-0”. All perimeter yard setback requirements are met. Historic review is a separate review from this building permit and is submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using Submission Type “Historic Review”. Historic review requirements and application can be found at: https://www.tucsonaz.gov/files/pdsd/Preservation/HPZ_Review_Application_Package_2020.pdf.

Additional comments:

1. Provide a lot coverage calculation that meets the requirements of UDC Article 6.4.3 and the example shown on the Residential Plot Plan Requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf. Per UDC TABLE 6.3-4.A: DIMENSIONAL STANDARDS FOR THE C-1, C-2, C-3, OCR-1, & OCR-2 ZONES, HC-3 Zone the maximum lot coverage is 80%.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
01/25/2022 SBLOOD1 ENGINEERING REVIEW Passed
01/25/2022 AWARNER1 NPPO REVIEW Passed
01/25/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Provide a complete plan set with new dwelling ordinance compliance after DDO approval.

Clarify each building address with labels on the site plan.
02/25/2022 JPEELDA1 FIRE REVIEW Reqs Change Provide a complete set of plans
Provide the complete under roof square footage
Provide a site plan

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033