Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM09909
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/02/2022 | PCAMARE1 | OIP | REVIEW | Reqs Change | FROM: Paul Camarena PDSD Residential Review Section PROJECT: T21CM09909 Rooftop Solar Panels 8165 E DOMENIC ST TRANSMITTAL DATE:?February ?2, ?2022 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed. COMMENT: Residential has reviewed the plan and cannot approve it at this time. Please address the following comments These comments are still applicable, Please provide a spec sheets for the solar hotwater heater. The line tap is located inside of the main service panel show a tap enclosure with sufficient space for the tap device such as a milbank tapping device. COMMENT: : After reviewing the aerials it has come to my attention that there is Solar or a Solar hot water heater existing on the roof. Please provide a permit for the existing equipment.. COMMENT: The Plan Set shows a line-side tap, Line taps require compliance with NEC 230.46. Update the plans showing a tap enclosure with sufficient space for the tap device, or show a meter socket extension with tap terminals (approved Milbank tapping device) COMMENT: Residential will review the application on the next submittal If you have any questions about this transmittal, Contact Paul Camarena any time during the week by phone (520)837-4986 or email Paul.camarena@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans . |