01/13/2022 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T21CM09909
Roof top Solar Panels (1st Review)
8165 E DOMENIC ST

TRANSMITTAL DATE: January 13, 2022



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments

COMMENT: : After reviewing the aerials it has come to my attention that there is Solar or a Solar hot water heater existing on the roof. Please provide a permit for the existing equipment..


COMMENT: The Plan Set shows a line-side tap, Line taps require compliance with NEC 230.46. Update the plans showing a tap enclosure with sufficient space for the tap device, or show a meter socket extension with tap terminals (approved Milbank tapping device)


COMMENT: Residential will review the application on the next submittal


If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans

Final Status

Task End Date Reviewer's Name Type of Review Description
01/13/2022 NGARCIA3 OUT TO CUSTOMER Completed