Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T21CM09907
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/30/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 09/02/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM09907 REV1 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Conditionally Approved NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances. BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: Denied 1. Roof hatch shall be located a minimum of 10' from roof edge or protected in an approved manner (MMC2018,304.11 2. Provide 2,000 cfm of outside air to basement , 2,000 cfm for outside air to 1st floor and 2,000 cfm to 2nd floor (MMC2015,403.3.1.1) 3. What type of forklifts are being used in this building electric or fuel (MMC2018,106.3.1) 4. Where FCU1-1 and 1-8 and FCU0-1 in basement share a common duct with a combined capacity of over 2,000 cfm both FCU's must be protected with a duct smoke detector (MMC2018,606.2.2) 5. Where FCU 1-5,1-6,1.4, and 1-3 and FCU 0-5 in basement share a common duct they all must be protected with a duct smoke detector (MMC2018,606.2.2) 6. Provide outside air flow for FCU's on sheet m0.1 it is missing (MMC2018,106.3.1) 7. Provide duct smoke detectors to all FCU that share a common duct fcu 1-2 and FCU 0-3. in basement and all floor's from basement to 2nd floor (MMC2015,606.2.2) 8. All intake louver's shall be 10' horizontally from or 25' above vents, streets, alleys. parking lots and loading docks (MMC2015,401.4 ELECTRICAL REVIEW COMMENTS N/A PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
| 09/21/2022 | JPEELDA1 | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/21/2022 | VVERA1 | OUT TO CUSTOMER | Completed |