Review Date Reviewer's Name Type of Review Description Status Comments
05/27/2022 DBENOIT1 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T21CM09907

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E1.0 BASEMENT LIGHTING PLAN: Should have/add exit signs directly over exit doors ie stairway doors. Comment applies
to other sheets.
E1.1 1ST FLOOR LIGHTING PLAN: South Stairwell should have Exit signs.
E2.1 1ST FLOOR POWER PLAN: Circuits for CP-1 not fully identified.
E2.3 3RD FLOOR POWER PLAN: Suggest some Service receptacles on this level

PLUMBING REVIEW COMMENTS:
Approved

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov