| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/27/2022 | DBENOIT1 | 2ND PARTY REVIEW | REVIEW | Approv-Cond | Activity Number: T21CM09907 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: Approved ELECTRICAL REVIEW COMMENTS Conditionally Approved E1.0 BASEMENT LIGHTING PLAN: Should have/add exit signs directly over exit doors ie stairway doors. Comment applies to other sheets. E1.1 1ST FLOOR LIGHTING PLAN: South Stairwell should have Exit signs. E2.1 1ST FLOOR POWER PLAN: Circuits for CP-1 not fully identified. E2.3 3RD FLOOR POWER PLAN: Suggest some Service receptacles on this level PLUMBING REVIEW COMMENTS: Approved If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |