Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T21CM09907
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/19/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
01/21/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM09907 4032 E Fort Lowell Rd – C-2 Personal Storage – (1st Review) TRANSMITTAL: January 21, 2022 This site is located in the C-2 zone (UDC 4.7.21). Personal Service is a permitted use in this zone (Table 4.8-4), subject to Use Specific Standards 4.9.10.C.3 & .6. 1. Zoning has reviewed the building plan for compliance with DP21-0173 and have the following comments that must be addressed prior to approval of this building plan. 2. The DP must be issued prior to approval of this building plan. 3. The development package sheets provided in the building plan set must either be the stamped approved plans, marked for reference only or removed from the building plan set. 4. Details 6 & 8 on sheet SP1.1 do not match what was approved on the DP. Revise one or the other so that they match or remove them from the building plan set. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov |
01/21/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
01/24/2022 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Sheet T1.0 in the Jurisdiction: it shows Scottsdale/Maricopa County instead of COT /Pima County. Deferred Submittals: Shall also reference : Building shall be tested for ERRC by PCWIN and the test results provided to TFD prior to TCO. Sheet DP3 of 19 shows # 30 as a gate provided by others. Gate requires a seperate permit and it shall be noted that it if electric will require a KNOX Key Switch and KNOX box at the gate. Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 |
01/24/2022 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Elevator shall be provided with two-way communication at the elevator landing. Provide documentation that the interior of the Elevator will be compliant with IBC 2018, Chapter 30 These notes go with my first comment. Jennifer Peel-Davis |
01/28/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM09907 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied 1. Provide Geotechnical Report for the proposed building per International Building Code 2018, Section 1803.1. 2. Verify the design lateral pressure from the surcharge loads are included in the lateral earth pressure load and design of the foundation wall as indicated in IBC 2018 Section 1610.1 BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: Denied 1. Elevator machine rooms, machinery spaces that contain the driving machine, and control rooms or spaces that contain the operation or motion controller for elevator operation shall be provided with an independent ventilation or air-conditioning system to protect against the overheating of the electrical equipment (IBC2018,3005.2) 2. Provide 1,984 cfm's to each floor for ventilation (IMC2018,403.3.1.1) 3. Guards shall be provided where appliances are located within 10' of a roof edge (IMC2018,304.11) ELECTRICAL REVIEW COMMENTS Conditionally Approved E1.0 BASEMENT LIGHTING PLAN: Should have/add exit signs directly over exit doors ie stairway doors. Comment applies to other sheets. E1.1 1ST FLOOR LIGHTING PLAN: South Stairwell should have Exit signs. E2.1 1ST FLOOR POWER PLAN: Circuits for CP-1 not fully identified. E2.3 3RD FLOOR POWER PLAN: Suggest some Service receptacles on this level PLUMBING REVIEW COMMENTS: Denied 1). Basement sump basin in detail #1 on P3.0 needs to be vented. update all affected pages. -IPC 712.3.2 2). 131 GPM 4" horizontal roof drain conductor shown on plan pg P1.4 & detail #18 on A8.0 needs 1/4" minimum pitch to comply with IPC Table 1106.2 3). Plan Pg. T1.0 Total occupant load 413 S-1 is 1 per 100 for toilets & lavs. That equals 3 toilets/lavs for men & 3 toilets/lavs for the women. Update all affected pages. -IPC 403.1 4). Add toilet & Lav sidewall wall to fixture center measurements to plan pg A2.1. -IPC 404.2 405.3.1 5). Add seismic straps to water heater detail on plan page P3.0. -IPC 502.4 6). Plans not clear on water supply connection for fire system. -IPC 608.17.4 |
02/03/2022 | SBLOOD1 | ENGINEERING | REVIEW | Reqs Change | 1. Zoning comments 3 and 4 need to be addressed before engineering can approve the building plan. Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/03/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |