Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM09887
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/03/2022 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
01/05/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
01/12/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
01/12/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The developed length of the hot water supply piping from the water heater to the new sinks appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2018 and C404.5, IECC 2018. 2. Provide cleanouts for all horizontal drains (i.e. a 2" cleanout at each hand sink). Reference: Section 708.1.1, IPC 2018. |
01/12/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
01/14/2022 | JVINCEN1 | FIRE | REVIEW | Approved | |
01/20/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
01/21/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
01/21/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |